| Operation of diagnostic function |
|
|
| ||
|
|
|
|
|
| |
Check |
| Status of |
|
|
| |
code |
|
|
|
| ||
| Cause of operation | air conditioner | Condition |
| Judgment and measures | |
Indoor |
| |||||
|
|
|
|
| ||
unit |
|
|
|
|
| |
|
|
|
|
| ||
H03 | Current detection circuit error | Stop | Displayed when | 1. Check outdoor P.C. board | ||
error is detected |
| (AC current detection circuit) | ||||
|
|
|
| |||
|
|
|
|
|
| |
| Open phase of |
| Displayed when | 1. | Check open phase of | |
P05 | Stop | 2. | Black lead wire to be connected to CN03 of | |||
error is detected | ||||||
| ||||||
|
|
|
|
| does not pass through T611. | |
|
|
|
|
|
| |
|
|
|
| 1. | Check connection of Ps sensor connector. | |
|
|
| Displayed when | 2. | Check failure of Ps sensor. | |
F23 | Ps sensor error | Stop | 3. | Check compressing power error of compressor. | ||
error is detected | ||||||
|
|
| 4. | Check | ||
|
|
|
| |||
|
|
|
| 5. | Check outdoor P.C. board error. | |
|
|
|
|
|
| |
|
|
|
| 1. | Check service valves are fully opened. | |
|
|
|
|
| (Gas side, Liquid side) | |
|
|
|
| 2. | Check clogging of outdoor PMV. (PMV1, 2) | |
|
|
| Displayed when | 3. | Check SV2 circuit. | |
H06 | Low pressure protective operation | Stop | 4. | Check Ps sensor error. | ||
error is detected | ||||||
|
|
|
| 5. | Check clogging of indoor filter. | |
|
|
|
| 6. | Check clogging of refrigerant pipe. | |
|
|
|
| 7. | Check of outdoor fan operation. (In heating mode) | |
|
|
|
| 8. | Check short of refrigerant. | |
|
|
|
|
|
| |
| Discharge temp. error |
| Displayed when | 1. | Check refrigerating cycle (Gas leak) | |
P03 | ∗ Discharge temp. (TD) over specified value | Stop | 2. | Trouble of electronic expansion valve | ||
error is detected | ||||||
| was detected.(1.6) |
| 3. | Check discharge temp. sensor (TD). | ||
|
|
| ||||
|
|
|
| |||
|
|
|
|
|
| |
|
|
|
| 1. | Check case thermostat and connector. | |
| Case thermostat operation |
| Displayed when | 2. | Check gas leak, recharge | |
H04 | Stop | 3. | Check full open of service valve. | |||
∗ Abnormal overheat of compressor | ||||||
error is detected | ||||||
|
| 4. | Check PMV (Pulse Motor Valve). | |||
|
|
|
| |||
|
|
|
| 5. | Check broken pipe. | |
|
|
|
|
|
| |
|
|
|
| 1. | Check service valves are fully opened. | |
|
|
|
|
| (Gas side, Liquid side) | |
|
|
|
| 2. | Check of outdoor fan operation. | |
|
|
|
| 3. | Check motor error of outdoor fan. | |
|
|
| Displayed when | 4. | Check clogging of outdoor PMV. (PMV1, 2) | |
P04 | High pressure SW system error | Stop | 5. | Check clogging of heat exchanger in indoor/outdoor units. | ||
error is detected | ||||||
|
|
| 6. | |||
|
|
|
| |||
|
|
|
| 7. | Check outdoor P.C. board error. | |
|
|
|
| 8. | Check fan system error (Cause of air volume drop) at | |
|
|
|
|
| indoor side. | |
|
|
|
| 9. | Check PMV opening status in indoor unit. | |
|
|
|
|
| ||
P05 | Power supply voltage error | Stop | Displayed when | 1. Check power supply voltage. | ||
error is detected |
|
| ||||
|
|
|
|
| ||
|
|
|
|
|
| |
| High pressure protective operation |
|
| 1. | Check outdoor heat exchanger sensor (TL). | |
|
|
| 2. | Check indoor heat exchanger sensor (TC, TCJ). | ||
| • During cooling operation, outdoor temp. |
|
| |||
|
|
| 3. | Check full open of service valve. | ||
| sensor (TL) detected temperature over |
|
| |||
P20 |
| Displayed when | 4. | Check indoor/outdoor fan. | ||
specified temp. | Stop | |||||
| error is detected | 5. | Check PMV (Pulse Motor Valve). | |||
| • During heating operation, indoor temp. |
| ||||
|
|
| ||||
|
|
| 6. | Check clogging and short circuit of indoor/outdoor heat | ||
| sensor (TC, TCJ) detected temperature over |
|
| |||
| specified temp. |
|
|
| exchanger. | |
|
|
|
| 7. | Overcharge of refrigerant. Recharge | |
|
|
|
|
|
| |
|
|
| Displayed when | 1. | Check lock of fan motor. | |
P22 | Outdoor fan system error | Stop | 2. Check power supply voltage between L2 and N. | |||
error is detected | ||||||
|
|
| 3. | Check outdoor P.C. board. | ||
|
|
|
| |||
|
|
|
|
|
| |
|
|
|
| 1. | When performing operation while | |
P26 | Stop | Displayed when |
| wire, P26 error occurs. Check control P.C. board. | ||
|
| |||||
element | error is detected | 2. | When performing operation while | |||
|
| |||||
|
|
|
|
| wire, an error does not occur. (Compressor rare short) | |
|
|
|
|
|
| |
P29 | Position detection circuit error | Stop | Displayed when | 1. | Check control P.C. board. | |
error is detected |
|
| ||||
|
|
|
|
| ||
|
|
|
|
|
|
– 50 –