Toshiba RAV-SM564MUT-TR 4, 5, 36, Item, Outline of specifications, Remarks, Ceiling type

Models: RAV-SM454MUT-TR RAV-SM564CT-E RAV-SM564BT-E RAV-SM564MUT-E RAV-SM564BT-TR RAV-SM564MUT-TR RAV-SM804BT-TR RAV-SM804BT-E RAV-SM1104BT-TR RAV-SM1404BT-TR RAV-SM1104BT-E RAV-SM1404BT-E RAV-SM404MUT-TR RAV-SM454MUT-E

1 120
Download 120 pages 15 Kb
Page 36
Image 36
4, 5, 6

No.

Item

 

 

 

Outline of specifications

 

 

 

Remarks

 

 

 

 

 

 

 

 

 

 

13

Frequency fixed

(Ceiling type)

 

 

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Test run)

 

Procedure

 

 

Description

 

 

(Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn on power of the air conditioner.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

The operation is not accepted for 5 minutes when power has been turned on at first time after

 

 

 

 

 

installation, and 1 minute when power has been turned on at the next time and after. After the

 

 

 

 

 

 

specified time has passed, perform a test operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

Push [Start/Stop] button and change the operation mode to [COOL] or [HEAT] with [Mode] button.

 

 

 

 

 

Then change the fan speed to [High] using [Fan] button.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Test cooling operation

 

 

Test heating operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set temperature to [18°C] using

 

 

Set temperature to [30°C] using

 

 

 

 

 

 

[Temperature set] button.

 

 

[Temperature set] button.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

After checking the receiving sound

 

 

After checking the receiving sound

 

 

 

 

 

“Pi”, immediately push [Temperature set]

 

 

“Pi”, immediately push [Temperature set]

 

 

 

 

 

button to set to [19°C]

 

 

button to set to [29°C].

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

After checking the receiving sound “Pi”,

 

 

After checking the receiving sound “Pi”,

 

 

 

 

 

immediately push [Temperature set] button

 

immediately push [Temperature set] button

 

 

 

 

 

to set to [18°C].

 

 

to set to [30°C].

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

Then repeat the procedure 45

4

5.

 

 

 

 

 

After approx. 10 seconds, all the display lamps on the sensor part of wireless remote controller,

 

 

 

 

 

[Operation] (Green), [Timer] (Green), and [Ready] (Yellow) flash and the air conditioner starts operation.

 

 

 

 

 

 

If the lamps do not flash, repeat the procedure 2 and after.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

After the test operation, push [Start/Stop] button to stop the operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<Outline of test operation from the wireless remote controller>

Test cooling operation:

Start 18°C 19°C 18°C 19°C 18°C 19°C 18°C (Test operation) Stop

Test heating operation:

Start 30°C 29°C 30°C 29°C 30°C 29°C 30°C (Test operation) Stop

Be sure to set the air speed to [High]

2

3,

4, 5, 6

 

2,

7

14 Filter sign display

1)

The operation time of the indoor fan is calculated, the filter

[FILTER ] goes on.

(Except wireless

 

reset signal is sent to the remote controller when the

 

type)

 

specified time (2500H) has passed, and it is displayed on

 

It is provided

 

LCD.

 

on the sepa-

2)

When the filter reset signal has been received from the

 

rately sold type

 

remote controller, time of the calculation timer is cleared.

 

TCB-AX21E2.

 

In this case, the measurement time is reset if the specified

 

 

 

time has passed, and display on LCD disappears.

 

 

 

 

 

– 36 –

Page 36
Image 36
Toshiba RAV-SM564MUT-TR, RAV-SM454MUT-E, RAV-SM404MUT-TR 4, 5, 36, Item, Outline of specifications, Remarks, Ceiling type