8. SETUP AT LOCAL SITE AND OTHERS
8-1. Indoor Unit
8-1-1. Test Run Setup on Remote Controller
<Wired remote controller>
1. When pushing TEST button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display.
Then push | ON / OFF button. |
•“TEST” is displayed on LC display during operation of Test Run.
•During Test Run, temperature cannot be adjusted but air volume can be selected.
•In heating and cooling operation, a command to fix the Test Run frequency is output.
•Detection of error is performed as usual. However, do not use this function except case of Test Run because it applies load on the unit.
2.Use either heating or cooling operation mode for [TEST].
NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after operation has stopped.
3.After a Test Run has finished, push TEST button again and check that [TEST] on LC display has gone off. (To prevent a continuous test run operation,
(Compact 4-way Cassette Type and Concealed Duct Type)
1 Remove a screw which fixes the serial olate of the receiver part on the wireless remote controller.
Remove the nameplate of the reciver section by inserting a minus screwdriver, etc. into the notch at the bottom of the plate, and set the Dip switch to [TEST RUN ON].
2 Execute a test operation with button on the wireless remote controller.
•, and LED flash during test operation.
•Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is invalid.
Notch Nameplate
Small screw