9-2-2. Automatic Address Example from Unset Address (No miswiring)

1. Standard (One outdoor unit)

1-1

Individual

(Header/Master)

(1-1)

1-2

Header/Master

(1-2)

1-1

Follower/Sub

(1-1)

1-2

Header/Sub

(1-2)

1-3

Follower/Master

(1-3)

1-1

Follower/Sub

Only turning on source power supply (Automatic completion)

2.Group operation

(Multiple outdoor units = Multiple indoor units with serial communication only, without twin)

2-1

Header/Sub

1-1

Header/Sub

3-1

Header/Master

8-1

Header/Sub

(Max. : 8 units)

Only turning on source power supply (Automatic completion)

3. Multiple groups operation

Single

Twin

Triple

2-1

Header/Sub

1-1

Header/Sub

2-3

Follower/Master

3-1

Header/Sub

3-3

Follower/Sub

1-2

Follower/Sub

Change is necessary

Manually change addresses of the multiple sub units

simultaneously from the remote controller.

2-1

1-1

1-2

3-1

3-2

3-3

– 85 –

Page 85
Image 85
Toshiba RAV-SM404MUT-TR, RAV-SM454MUT-E, RAV-SM1404BT-E Automatic Address Example from Unset Address No miswiring