<Procedure> Perform setup while the unit stops.

6. External view of P.C. board assembly

Terminator (SW01)

52

85

7.Address setup

In addition to set up the central control address, it is necessary to change the indoor unit number. (Line/Indoor/Group address). For details, refer to 1:1 model connection interface Installation Manual.

8-3. How to Set up Central Control Address Number

When connecting the indoor unit to the central control remote controller using 1:1 model connection interface, it is necessary to set up the central control address number.

• The central control address number is displayed as the line No. of the central control remote controller.

How to set up from indoor unit side by remote controller

<Procedure> Perform setup while the unit stops.

1

2

3

Push TEST + VENT buttons for 4 seconds or more.

When group control is executed, first the unit No. (Fig.1)3 is displayed and all the indoor units in the group control are selected. In this time, fans of all the selected indoor units are turned on. (Fig. 1)

(Keep – 80 –Manual background displayed status without pushing UNIT LOUVER button.)

In case of individual remote controller which is not group-controlled, Line address and Indoor unit address are displayed.

Using temperature setup Manual backgroundTEMP. buttons, specify CODE No. ￿!.

Using timer time TIME buttons, select the SET DATA.

The setup data is shown in the table below (Table 1).

4 Push SET button. (OK if display goes on.)

• To change the item to be set up, return to Procedure 2.

5 Push TEST button.

The status returns to usual stop status.

(Table 1)

SET DATA

Central control address No.

2

 

 

0001

1

0002

2

1

0003

3

:

:

 

0064

64

 

 

 

5

0099

Unset (Setup at shipment from factory)

 

 

(Fig.1)

 

 

 

 

CODE No.

SET DATA SETTING

 

 

 

 

 

UNIT

No.

 

 

 

R.C.

No.

 

TEMP.

 

 

 

ON / OFF

 

TIMER SET

 

FAN

MODE

 

TIME

 

SAVE

VENT

FILTER

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

3

1

4

– 80 –