Toshiba RAV-SM454MUT-E, RAV-SM404MUT-TR, RAV-SM1404BT-E, RAV-SM1104BT-E P10 error, F10 error

Models: RAV-SM454MUT-TR RAV-SM564CT-E RAV-SM564BT-E RAV-SM564MUT-E RAV-SM564BT-TR RAV-SM564MUT-TR RAV-SM804BT-TR RAV-SM804BT-E RAV-SM1104BT-TR RAV-SM1404BT-TR RAV-SM1104BT-E RAV-SM1404BT-E RAV-SM404MUT-TR RAV-SM454MUT-E

1 120
Download 120 pages 15 Kb
Page 56
Image 56
[P10 error]

[P10 error]

Is connection of

float switch connector NO (Indoor control board CN34)

normal?

YES

NO

YES

Correct connection

of connector.

 

Does float switch work?

 

 

 

 

Is circuit wiring normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

Check and correct wiring

 

 

 

 

 

 

 

 

 

 

 

Does drain pump work?

 

and wire circuit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

Are connector pins 1 and 3

NO

 

 

 

 

Is power of

 

 

 

 

 

 

 

 

 

 

 

 

 

at drain pump unit side shorted

 

 

 

 

drain pump turned on?

 

 

 

 

 

 

 

 

(Resistance value 0)?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace drain pump

 

 

 

 

Check the drain pipe, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and indoor P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(MCC-1402).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace drain pump.

 

 

 

Check indoor P.C. board

 

 

 

 

 

(MCC-1402).

 

 

Check wiring.

 

 

 

 

 

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check that voltage of 1 – 3 pin of CN068 on the indoor P.C. board is 220–240V.

[F10 error]

Is connection of TAsensor connector

NO

 

(indoor P.C. board CN104) nornal?

 

 

 

YES

 

 

 

 

NO

 

 

Are characteristics of TA sensor resistance value normal?

YES

Refer to Characteristics-1.

Connect connector

of connector.

Replace TA sensor.

Check indoor P.C. board (MCC-1402).

Defective Replace

– 56 –

Page 56
Image 56
Toshiba RAV-SM454MUT-E, RAV-SM404MUT-TR, RAV-SM1404BT-E, RAV-SM1104BT-E, RAV-SM1404BT-TR, RAV-SM1104BT-TR P10 error, F10 error