<Ceiling Type>

Procedure

Description

 

 

 

 

Turn on power of the air conditioner.

 

1

 

 

The operation is not accepted for 5 minutes when power has been turned on at first time after installation,

 

and 1 minute when power has been turned on at the next time and after. After the specified time has

 

passed, perform a test operation.

 

 

 

 

2

Push [Start/Stop] button and change the operation mode to [COOL] or [HEAT] with [Mode] button.

Then change the fan speed to [High] using [Fan] button.

 

 

 

 

Test cooling operation

Test heating operation

3

 

 

Set temperature to [18°C] using [Temperature set]

Set temperature to [30°C] using [Temperature set]

 

button.

button.

 

 

 

4

After checking the receiving sound “Pi”, immediately

After checking the receiving sound “Pi”, immediately

push [Temperature set] button to set to [19°C]

push [Temperature set] button to set to [29°C].

 

 

 

5

After checking the receiving sound “Pi”, immediately

After checking the receiving sound “Pi”, immediately

push [Temperature set] button to set to [18°C].

push [Temperature set] button to set to [30°C].

 

 

 

 

Then repeat the procedure 4 5 4 5 .

 

6

After approx. 10 seconds, all the display lamps on the sensor part of wireless remote controller,

[Operation] (Green), [Timer] (Green), and [Ready] (Yellow) flash and the air conditioner starts operation.

 

If the lamps do not flash, repeat the procedure 2 and after.

7

After the test operation, push [Start/Stop] button to stop the operation.

<Outline of test operation from the wireless remote controller>

Test cooling operation:

Start 18°C 19°C 18°C 19°C 18°C 19°C 18°C (Test operation) Stop

Test heating operation:

Start 30°C 29°C 30°C 29°C 30°C 29°C 30°C (Test operation) Stop

Be sure to set the air speed to [High]

2

3,

4, 5, 6

 

2,

7

– 69 –

Page 69
Image 69
Toshiba RAV-SM454MUT-TR, RAV-SM454MUT-E, RAV-SM804BT-E Procedure Description, Test cooling operation Test heating operation