E6581373

The relationship between the network variables and input terminals is shown in below.

Variables

LIU007Z

LIU006Z

nvoDigitalIn1

F terminal

 

 

nvoDigitalIn2

R terminal

 

 

nvoDigitalIn3

-------

 

 

 

Under Development

 

nvoDigitalIn4

-------

 

nvoDigitalIn5

 

 

 

-------

 

 

nvoDigitalIn6

-------

 

 

nvoDigitalIn7

-------

 

 

nvoDigitalIn8

-------

 

 

6.6.16. nvoAnalogIn1 to 3 (Analog Input Monitor)

Output network variable

SNVT type: SNVT_lev_percent (81)

They provide the inverter analog input terminal state in percentage.

-Valid range: 0.000 to 100.000%

-Unit: 0.005% (The resolution depends on the inverter specification)

The adjustment of analog input value is possible to set the inverter parameter (f470 to f475) (Refer to the inverter instruction manual for details).

The relationship between the network variable and the terminal is shown in the table below.

Name

LIU007Z

 

LIU006Z

nvoAnalogIn1

-----

 

 

 

 

Under development

 

nvoAnalogIn2

VIB terminal

 

 

nvoAnalogIn3

-----

 

 

 

 

 

 

When RR/S4 terminal has Logic input terminal function, “nvoAnalogIn1” always shows 0.000%.

6.6.17. nvoEmergStatus (Emergency Status)

Output network variable

SNVT type: SNVT_have_emerg (103)

It provides the response against an emergency stop of the inverter (nviEmergOverride). When the node received “nviEmergOverride” network variable, it propagates the information to the network.

- Valid range

Value

Status

Description

0

Trip release

EMERG_NORMAL (No Emergency mode)

1

 

EMERG_PRESSURIZE (Emergency pressurize mode)

2

 

EMERG_DEPRESSURIZE (Emergency depressurize mode)

3

Emergency stop

EMERG_PURGE (Emergency purge mode)

4

EMERG_SHUTDOWN (Emergency shutdown mode)

 

5

 

EMERG_FIRE (Emergency fire mode)

6 to 255

 

---

- 31 -

Page 32
Image 32
Toshiba TOSVERT VF-FS1 Series instruction manual NvoAnalogIn1 to 3 Analog Input Monitor, NvoEmergStatus Emergency Status