Toshiba TOSVERT VF-FS1 Series NviParamCmd Parameter access, Lnrecall, Lnlearncurrent

Models: TOSVERT VF-FS1 Series

1 38
Download 38 pages 40.49 Kb
Page 27
Image 27

E6581373

6.5.9. nviParamCmd (Parameter access)

Input network variable

SNVT type: SNVT_preset (94)

It is used to access the inverter parameters. Refer to section 7.5 “Parameter access method” for the example usage.

-Valid range: All accessible parameters in the inverter

-Format:

field

Length

 

Description

 

 

Command

 

 

 

0

(LN_RECALL)

: Not support

learn

1 byte

1

(LN_LEARN_CURRENT)

: Not support

 

 

2

(LN_LEARN_VALUE)

: Write

 

 

3

(LN_REPORT_VALUE)

: Read

selector

2 bytes

Parameter address (unsigned value) *1

value[0]

1 byte

0

 

 

value[1]

1 byte

0

 

 

value[2]

1 byte

The most significant 2 hex bytes of data

value[3]

1 byte

The least significant 2 hex bytes of data

day

2 bytes

Invalid *2

 

hour

1 byte

Invalid *2

 

minute

1 byte

Invalid *2

 

second

1 byte

Invalid *2

 

millisecond

2 bytes

Invalid *2

 

*1: This value is Hexadecimal value, but it may be displayed with decimal value on network tool.

*2: The time fields (day, hour, minute, second and millisecond) are not supported by this option unit. Any values in the time fields of the Parameter access command will be ignored.