Toshiba TOSVERT VF-FS1 Series Example usage, Procedure, Binding, Option unit reset method

Models: TOSVERT VF-FS1 Series

1 38
Download 38 pages 40.49 Kb
Page 34
Image 34

E6581373

7. Example usage

7.1. Procedure

Lower example shows the procedure to send the 100% speed drive command to the inverter. 1. Commission

Make a network tool to identify this option by using service pin function (refer to network tool manual in detail).

2. Binding

Refer to next section. 3. Configurations

Set correct value into the configuration properties. 4. Local/Remote

Confirm that the inverter is in Remote control mode. Otherwise set Remote control mode. 5. Drive command and setpoint

Set the {200, 1} (100% speed drive) into the nviDrvSpeedStpt and propagate it.

7.2. Binding

Network variable bound to the other network variable can transmit/receive the data. “Binding” can be made by network tool. Network variable has a direction (Input/Output) and individual type (SNVT_type). Binding to the same direction variable or the different type is prohibited.

Example connection

Fan Coil Unit

Bind

ACMotorDrive

 

Building

Controller

 

functional block

 

Management

 

 

 

 

 

system

nvoFanSpeed

 

nviDrvSpeedStpt

 

 

SNVT_switch

 

SNVT_switch

 

 

 

 

nvoDrvSpeed

nviDrvSpeed

 

 

 

 

 

_lev_percent

 

 

SNVT_lev_percent

SNVT

Bind

7.3. Option unit reset method

One method to reset the option unit is cycling the inverter power source. The other is using reset command by network tool.

- 33 -

Page 34
Image 34
Toshiba TOSVERT VF-FS1 Series instruction manual Example usage, Procedure, Binding, Option unit reset method