- Example 3: Illegal access

Illegal data is written to the inverter parameter f171, (Base frequency voltage, address 0171). The upper limit value is 330.0V (200V class). In case of writing 360.0V, the unit of this parameter is 0.1V and the data value is converted to hexadecimal, so the value is 0E10 hex. The controller node sends/receives the following data (out of range error).

Field

Send (nviParamCmd)

Receive (nviParamResp)

learn

LN_LEARN_VALUE

LN_LEARN_VALUE

selector

0171 hex

0171 hex

value[0]

00 hex

FF hex

value[1]

00 hex

00 hex

value[2]

0E hex

00 hex

value[3]

10 hex

03 hex

day ,hour, minute,

N/A

0

second, millisecond

 

 