Toshiba TOSVERT VF-FS1 Series instruction manual NviAnalogOut1,2 Control of Analog output

Models: TOSVERT VF-FS1 Series

1 38
Download 38 pages 40.49 Kb
Page 26
Image 26

E6581373

- Valid range

Bit

 

LIU007Z

 

 

LIU006Z

Terminal

 

Parameter

Terminal

Parameter

 

 

0

---

 

---

 

 

 

 

1

---

 

---

 

 

 

 

2

---

 

---

 

 

 

 

 

 

Under

Development

 

3

---

 

---

 

 

4

---

 

---

 

 

 

 

 

 

 

 

 

5

---

 

---

 

 

 

 

6-15

---

 

---

 

 

 

 

If multiple digital output control signals are used at the same time, the output value is the OR of all digital output controls.

6.5.7. nviAnalogOut1,2 (Control of Analog output)

Input network variable (Reserved) SNVT type: SNVT_lev_percent (81) They enable the analog output control.

- Valid range: 0.000 to 100.000%

(Output value is not adjusted by the inverter parameter “fm”, ”am”) - Unit: 0.005% (The resolution depends on the inverter specification)

When the variables will be used, the inverter parameters must be assigned.

Name

LIU007Z

 

LIU006Z

Terminal

Parameter

 

Terminal

 

Parameter

 

 

 

 

 

nviAnalogOut1

---

---

 

Under

Development

 

nviAnalogOut2

---

---

 

 

 

 

 

 

 

 

 

 

6.5.8. nviEmergOverride (Emergency stop)

Input network variable

SNVT type: SNVT_have_emerg (103)

It provides an emergency stop of the motor. Emergency stop can be configured by Emergency stop selection (f603) to coast stop, slow down stop or emergency DC braking (refer to the inverter instruction manual for details).

- Valid range

Value

Command

Description

0

Remove emergency

EMERG_NORMAL (No Emergency mode)

1

 

EMERG_PRESSURIZE (Emergency pressurize mode)

2

 

EMERG_DEPRESSURIZE (Emergency depressurize mode)

3

Emergency stop

EMERG_PURGE (Emergency purge mode)

4

EMERG_SHUTDOWN (Emergency shutdown mode)

 

5

 

EMERG_FIRE (Emergency fire mode)

6 to 255

 

---

N.B.: “Remove emergency” command clears a fault and resets the inverter.

- 25 -