E6581373

3.7. Reference parameter of the inverter

Reference parameter of the inverter is listed below.

Title

 

Name

Description

acc

 

Acceleration time

 

dec

 

Deceleration time

 

fh

 

Maximum frequency

Do not change these parameters, because

ul

 

Upper limit frequency

the LONWORKS option unit using them.

ll

 

Lower limit frequency

 

vl

 

Base frequency 1

 

 

 

 

Network command has priority when the

cmod

 

Command mode selection

inverter is Remote mode. (See previous

 

 

 

section)

 

 

 

Network setpoint has priority when the

fmod

 

Setpoint mode selection

inverter is Remote mode. (See previous

 

 

 

section)

f111

...

Logic input terminal function

Set proper value if use (See the inverter

instruction manual).

 

 

 

f603

 

Emergency stop selection

For “nviEmergOverride”

f800

 

Communication baud rate

Set “1” (default)

f801

 

Communication parity

Set “1” (default)

f803

 

Communication error trip time

Set properly value

f829

 

Communication protocol

Set “1” (MODBUS)

 

 

 

 

f851

 

Operation at network disconnection

See “section 7.4 Communication health

 

management”.

 

 

 

Warning

Mandatory

For LIU007Z, set up “Communication error trip function (f803, see the inverter instruction manual for details)” to stop the inverter when this option unit is deactivated by an unusual event such as tripping, an operating error, power outage, failure, etc. Deactivated option unit may cause an accident, if the “Communication error trip function” is not properly set up.

- 11 -

Page 12
Image 12
Toshiba TOSVERT VF-FS1 Series instruction manual Reference parameter of the inverter