E6581373
6.6.18. nvoParamResp (Parameter Access Response)
Output network variable SNVT type: SNVT_preset (94)
It provides to the response of the inverter parameters accessing (nviParamCmd). Refer to section 7.5 “Parameter access method” for the example usage.
- Format
field | Length | Description | ||
|
| Command |
| |
learn | 1 byte | 2 (LN_LEARN_VALUE) | : Write | |
3 (LN_REPORT_VALUE) | : Read | |||
|
| |||
|
| the other | : Not support | |
|
|
| ||
selector | 2 bytes | Parameter address (unsigned value) *1 | ||
value[0] | 1 byte | 0 at successful, FFh at occurred error *2 | ||
value[1] | 1 byte | 0 |
| |
value[2] | 1 byte | The most significant 2 hex bytes of data | ||
value[3] | 1 byte | The least significant 2 hex bytes of data | ||
day | 2 bytes | 0 |
| |
hour | 1 byte | 0 |
| |
minute | 1 byte | 0 |
| |
second | 1 byte | 0 |
| |
millisecond | 2 bytes | 0 |
|
*1: This value may be displayed with decimal value on network tool
*2: When access error occurred, “value[0]” field shows FFh and the error code is shown in “value[3]” field.
01h: Illegal function for the addressed node
02h: Illegal parameter address
03h: Illegal data value
04h: Illegal access (cf. prohibit writing)
6.6.19. nvoTypeVer (Identification)
Output network variable
SNVT type: SNVT_str_asc (36) polled
It provides the inverter identification data (Brand, Commercial Reference, Version) by Ascii code. Null The string is ended by Null terminator (“ 0”). This variable can be read only with polling.
- Structure
Data | Length | Description | ASCII |
Vendor name | 7 | “TOSHIBA” | |
space | 1 | Character “space” | 0x20 |
Product code | free | ||
space | 1 | Character “space” | 0x20 |
v | 1 | Character “V” | 0x56 |
major revision | 1 | Software version (major) | |
. | 1 | Character “.” | 0x2E |
minor revision | 2 | Software version (minor) |
Ex. “TOSHIBA
- 32 -