E6581373

6.2. Network variable list (VSD_6010_11)

LONWORKS option unit supports all mandatory network variables included in LONMARK functional profile “Variable Speed Motor Drive”. The network variables are shown in the table below.

“nvi” means an input network variables, “nvo” means an output network variables and “nci” means a network configuration properties.

LIU

LIU

Variables

SNVT_type.

unit

007Z

006Z

 

 

 

v

 

nviDrvSpeedStpt

SNVT_switch

0.5%,1

v

 

nvoDrvSpeed

SNVT_lev_percent

0.005%

v nviDrvSpeedScale SNVT_lev_percent 0.005%

v

 

nvoDrvCurnt

SNVT_amp

0.1A

---

 

nvoDrvVolt

SNVT_volt

0.1V

---

 

nvoDrvPwr

SNVT_power_kilo

0.1kW

v

 

nvoDrvRunHours

SNVT_time_hour

1h

---

 

nciLocation

SNVT_str_asc

Ascii

v

 

nciMaxSpeed

SNVT_lev_percent

0.005%

v

 

nciMinSpeed

SNVT_lev_percent

0.005%

v

 

nciRcvHrtBt

SNVT_time_sec

0.1s

v

 

nciSndHrtBt

SNVT_time_sec

0.1s

v

 

nciMinOutTm

SNVT_time_sec

0.1s

v

 

nciNmlSpeed

SNVT_rpm

1min-1

v

 

nciNmlFreq

SNVT_freq_hz

0.1Hz

v

 

nciRampUpTm

SNVT_time_sec

0.1s

v

 

nciRampDownTm

SNVT_time_sec

0.1s

v nciDrvSpeedScale SNVT_lev_percent 0.005%

v: Support, ---: Not support.

Default value

{0.0%, -1}

nciDrvSpeedScale

100.000%

0.000%

0.0s

0.0s

0.5s 1800min-160Hz 10.0s 10.0s 100.000%

LONMARK

Mandatory

Mandatory

Optional

Optional

Optional

Optional

Optional

Optional

Mandatory

Mandatory

Optional

Mandatory

Optional

Mandatory

Mandatory

Mandatory

Mandatory

Optional

*LIU006Z is under development.

- 17 -

Page 18
Image 18
Toshiba TOSVERT VF-FS1 Series instruction manual Network variable list VSD601011, Liu