6.4.9. nciRampDownTm (Ramp Down Time)

Configuration property, Variable Speed Drive 6010_11 (Mandatory)

SNVT type: SNVT_time_sec (107)

SCPT reference: SCPTrampDownTm (161)

It determines the ramp down time of the motor.

-Valid range: 0.1 to 3200.0 sec.

-Unit: 0.1 sec.

-Default value: 10.0 sec.

N.B.: By editing this variable, this option unit changes the inverter parameter “dec” automatically.

6.4.10. nciDrvSpeedScale (Default value for nviDrvSpeedScale)

Configuration property, Variable Speed Drive 6010_11 (Optional) SNVT type: SNVT_lev_percent (81)

SCPT reference: SCPTdefScale (162)

It is used as the default value for “nviDrvSpeedScale”. When this option unit is initialized, it will be updated.

-Valid range: -163.840 to 163.830%

-Unit: 0.005%

-Default value: 100.000%

6.4.11.nciPwUpOutTm (Power up delay time).

Configuration property

SNVT type: SNVT_time_sec (107)

SCPT reference: SCPTpwrUpDelay (72)

It defines the time until starting transmission after the device powered up. It is useful to improve network traffic at power-up.

-Valid range: 0.0 to 300.0 sec (If the value exceed 300.0, the value is limited to 300.0 sec)

-Unit: 0.1 sec.

-Default value: 0.0 sec.