Mechanical Specifications
General
Units shall be specifically designed for outdoor air handler installation on a roof curb and be completely factory assembled and tested, piped, internally wired and shipped in one piece.
Air handlers shall be available as either no cooling or chilled water cooling units. Heat options include natural gas, electric, hot water, steam or no heat. Filters, outside air system, exhaust air system, optional
positive latching at three points. Access doors shall provide a door stop mechanism to latch the door in the open position to prevent unsafe door closure by wind.
Doors of laminated double wall construction with a polyurethane foam core between the exterior sheet metal pane and the interior liner, with an insulating value of R8 shall be provided on the air handler's serviceable compartments such as return/exhaust fan, filters, coil and blank sections. Two single wall doors shall be provided for access to the control panel.
Electrical System
Convenience Outlet
A 15A, 115V Ground Fault Interrupter convenience outlet shall be wired and powered from a factory mounted transformer. A unit mounted,
Non-Fused Disconnect Switch
An external handle mounted on the control box door shall be provided to disconnect unit power.
All units shall be UL/CSA approved and factory run tested. All units shall also be compliant with IBC Seismic requirements. All units shall have decals and tags to aid in service and indicate caution areas. Electrical diagrams shall be printed on long life water resistant material and shall ship attached to control panel doors.
Casing
Exterior panels shall be zinc coated galvanized steel, phosphatized and painted with a slate grey
The Air Handler shall be laminated
Access Doors
Access doors shall be hinged with a single, exterior mounted, height and tension adjustable, handle to provide
Blank Sections
A four or eight foot blank section of laminated double wall construction with a polyurethane foam core between the exterior sheet metal panel and the interior liner, with an insulating value of R8 shall be provided with similarly built, hinged, access doors on either side
Airflow Path
Unit shall have downflow discharge conditioned air path or horizontal discharge. Return airflow path shall be either upflow or horizontal.
Burglar Bar
A grate system shall be installed in supply and return air duct connection areas on
Belt Guard
Supply and exhaust fans shall have a universal size belt guard to accommodate any applicable drive configuration. The guard totally encloses the drive system and is provided with a
Unit Interrupt Rating
A 65000 Amp rating (480V) and 25000 Amp rating (600V) shall be applied to the unit enclosure using a
Marine Lights (Customer Powered)
A 120V master light switch shall be factory installed in the main unit control box for lighting control. The master switch shall be wired into an isolated terminal block with access for customer provided service. Marine light fixtures shall be supplied with 150W incandescent bulbs. Marine light fixtures shall be placed in the Supply Section (2), Fresh Air Section (1), Return Section (1), and Extended Casing Section (1) for units without Heat.
Supply/Exhaust/Return Motors
Supply, exhaust/return motors are either standard efficiency open drip- proof, high efficiency open drip- proof, or high efficiency totally enclosed fan cooled. All supply, exhaust/return motors meet the U.S. Energy Policy Act of 1992 (EPACT).