General Data

Table 3 General Data (All dimensions in inches)

 

Casing A

Casing B

Casing C

Supply Fans Std CFM

 

 

 

Number/Size/Type

1/25/ DW AF

1/32/ DW AF

1 / 36 DW AF

Number of Motors

1

1

1

HP Range

15 - 50

15 - 60

15 - 75

CFM Range/CFM at Max SP

16000-31000/22000

20000-38000/32000

23000-45000/40000

Total SP Range-(In. WG)

7.5

7.5

7.5

 

 

 

 

Exhaust Fans Std CFM

 

 

 

Number/Size/Type

1/25/ DW FC

1/28/ DW FC

1 / 32 DW FC

Number of Motors

1

1

1

HP Range

7.5 - 25 hp

7.5 - 50 hp

15 - 60 hp

CFM Range/CFM at Max SP

10000-28000/24000

13000-35000/30000

23000-40000/40000

ESP Range-(In. WG)

2.5

2.5

2.5

 

 

 

 

Exhaust Fans Low CFM

 

 

 

Number/Size/Type

-

1/25/ DW FC

1/28/ DW FC

Number of Motors

-

1

1

HP Range

-

7.5 - 25 hp

7.5 - 50 hp

CFM Range/CFM at Max SP

-

10000-28000/24000

13000-35000/30000

ESP Range-(In. WG)

-

2.5

2.5

 

 

 

 

Return Fans Std CFM

 

 

 

Number/Size/Type

1/36/ Plenum

1 / 40 Plenum AF

1 / 44.5 Plenum AF

Number of Motors

1

1

1

HP Range

7.5 - 40 hp

10 - 40 hp

10 - 40 hp

CFM Range/CFM at Max SP

16000-31000

20000-38000

23000- 44000/39000

ESP Range-(In. WG)

2.5

2.5

2.5

 

 

 

 

Electric Heat (60 Hz)

 

 

 

kw

90-265

90-300

140-300

Circuit Capacity Steps

30 - 37.5 kW

30 - 37.5 kW

35 - 37.5 kW

 

 

 

 

Natural Gas Heat

 

 

 

2-Stage Gas Heat

 

 

 

Low Heat Input (MBH)

850

850

850

Mid Heat Input/Output (MBH)

1100

1100

1100

High Heat Input/Output (MBH)

1800

1800

1800

Standard Heating Capacity Steps

2

2

2

 

 

 

 

Fully Modulating Steps

 

 

 

Low Heat Input (MBH)

10:1

10:1

10:1

Mid Heat Input (MBH)

20:1

20:1

20:1

High Heat Input (MBH)

20:1

20:1

20:1

 

 

 

 

Heat Exchanger Material

Stainless Steel

Stainless Steel

Stainless Steel

Chilled Water Coil

 

 

 

Size (inches)

42 x 115

42 x 115

42 x 115

Rows

2, 4, 6, or 8

2, 4, 6, or 8

2, 4, 6, or 8

Quantity

2

2

2

Type

5W, W, or WD

5W, W, or WD

5W, W, or WD

Fin Series

80, 108, 144, or 168

80, 108, 144, or 168

80, 108, 144, or 168

Turbulators

Turbulators Available

Turbulators Available

Turbulators Available

 

 

 

 

Hot Water Coil

 

 

 

Size

33 x 88 x 2 rows

33 x 88 x 2 rows

33 x 88 x 2 rows

Quantity

2

2

2

Type

5W, PrimaFlo

5W, PrimaFlo

5W, PrimaFlo

High Heat (fins/ft)

122

122

122

Low Heat (fins/ft)

80

80

80

 

 

 

 

Steam Coil

 

 

 

Size

33 x 88 x 1 row

33 x 88 x 1 row

33 x 110 x 1 row

Quantity

2

2

2

Type

NS, SigmaFlo

NS, SigmaFlo

NS, SigmaFlo

High Heat (fins/ft)

112

112

112

Low Heat (fins/ft)

62

62

62

 

 

 

 

34

RT-PRC031-EN