Controls
Variable Air Volume (VAV) Only
Figure 11. IntelliPak™ II Control Panel
Bypass control is offered to provide full nominal airflow in the event of drive failure.
Supply Air Static Pressure Limit
The opening of VAV terminals, and the amount of supply air provided by the inlet guide vanes, or variable frequency drive are coordinated during start up and transition to/from Occupied/Unoccupied modes to prevent over pressurization of the supply air ductwork.
However, if for any reason the supply air pressure exceeds the user- defined supply air static pressure limit that was set at the Human Interface Panel, the supply fan/VFD is shut down and the inlet guide vanes
VAV Units Only
Note: When noted in this sequence “Human Interface Panel,” the reference is to both the unit mounted and remote mounted Human Interface Panel. All setpoint adjustments can be accomplished at the unit or Remote Human Interface Panel.
When in any position other than full open, the vanes
(if included) are closed.
The unit is then allowed to restart three times. If the over pressurization condition occurs on the third time, the unit is shut down and a manual reset diagnostic is set and displayed at the Human Interface Panel and BAS/Network.
Supply Air Temperature Controls
Supply Air Pressure Control
Inlet Guide Vanes Control
Inlet guide vanes are driven by a modulating
The range is determined by the supply air pressure setpoint and supply air pressure deadband, which are set through the Human Interface Panel or BAS/Network.
Inlet guide vane assemblies installed on the supply fan inlets regulate fan capacity and limit horsepower at lower system air requirements.
Variable Frequency Drive (VFD) Control
Variable frequency drives are driven by a modulating
The range is determined by the supply air pressure setpoint and supply air pressure deadband, which are set through the Human Interface Panel or BAS/Network.
Variable frequency drives provide supply fan motor speed modulation. The drive will accelerate or decelerate as required to maintain the supply static pressure setpoint. When subjected to high ambient return conditions the VFD will reduce its output frequency to maintain operation.
Cooling/Economizer
During Occupied cooling mode of operation, the economizer (if available) and cooling are used to control the supply air temperature. The supply air temperature setpoint and deadband are
The supply air temperature setpoint may be
On units with economizer, a call for cooling will modulate the fresh air dampers open. The rate of economizer modulation is based on deviation of the supply air
11 |