Mechanical Specifications
MERV 14,
Pressure Drop, Totally
Incinerable, Cartridge, Final Filter
Option
Note: Available on cooling only units with four or
MERV 14,
Temperature Rated, Cartridge,
Final Filter Option
Note: Available on gas and electric heat units with
MERV 17, 99.97 Percent, Standard
Temperature Rated, HEPA, Final
Filter Option
Note: Available on cooling only units with four or
Filters shall be mounted in a galvanized steel filter frame bank.
MERV 17, 99.97 Percent, High
Temperature Rated, HEPA, Final
Filter Option
Note: Available on gas and electric heat units with
Exhaust Air
General
Exhaust air options shall include no relief, 100 percent modulating exhaust fan and 100 percent modulating exhaust fan with direct space building pressurization control.
Exhaust fans shall be either standard or low airflow
No Relief (Standard)
Relief air opening shall be sealed with panel and made watertight.
100 Percent Modulating Exhaust Fan Option
Fan design shall be double width, double inlet
Fan motor and assembly shall be mounted on common base to allow consistent belt tension with no relative motion between fan and motor shafts. The entire assembly
shall be completely isolated from unit with
100 Percent Modulating Exhaust Fan with Statitrac™ Control Option
Fan design shall be double width, double inlet
Fan motor and assembly shall be mounted on common base to allow consistent belt tension with no relative motion between fan and motor shafts. The entire assembly shall be completely isolated from unit with
A differential pressure control system, (Statitrac), shall use a differential pressure transducer to compare indoor building pressure to outdoor ambient atmospheric pressure. The FC exhaust fan shall be turned on when required to lower building static pressure setpoint. The (Statitrac) control system shall then modulate the discharge dampers (or VFD) to control the building pressure to within the adjustable, specified deadband that shall be adjustable at the Human Interface Panel.
103 |