Controls VAV and CV

 

Design

Space CO2 Level

 

 

 

Min OA

 

 

Damper

 

Minimum

Setpoint

 

 

Min OA

 

 

 

 

Damper

 

 

Position

Damper

DCV Min

Target

 

 

OA

 

 

Damper

 

OA

Setpoint

 

 

 

 

CO2 Min

CO2 Design

 

Setpoint

Setpoint

CO2 Level

Figure 14. CO2 Control

Twinning requires an LCI module installed in each unit and is accomplished by binding variables between unit communication modules, communicating common setpoints and conditions (temperatures, pressures, fan speeds, damper positions, occupancy, states, etc.) and allowing each unit to run independent algorithms.

Twinned units must share a common supply and return duct network.

Twinned units operate:

a.as part of a Trane ICS™ installation, with Tracer Summit

b.on an interoperable project with a 3rd party LonTalk

c.as an independent group (bound via Rover® or 3rd party tool).

If there is a call for economizer cooling, the outdoor air damper may be opened further to satisfy the cooling request.

If the space CO2 level is greater than the CO2 Minimum Setpoint and less than the CO2 Design Setpoint, the outdoor air damper position is (or OA flow) modulated proportionally to the Space CO2 level relative to a point between the CO2 Min Setpoint and the CO2 Design Setpoint. If there is a call for economizer cooling, the outdoor air damper may be opened further to satisfy the cooling request. See Figure 14, p. 21

Humidification Control

A relay output is provided to control an externally connected, field supplied humidifier. Logic is provided for Occupied and Unoccupied humidification control with safeguards to prevent cycling between humidification and dehumidification

other cases the return fan is turned on or off with the supply fan.

LonTalk® Building

Automation System

The LonTalk Communication Interface for IntelliPak II (LCI-I) controller expands communications from the unit UCM network to a Trane Tracer Summit or a 3rd party building automation system, utilizing LonTalk, and allows external setpoint and configuration adjustment and monitoring of status and diagnostics. The LCI-I utilizes an FTT-10A Free Topology transceiver, which supports non-polarity sensitive, free topology wiring, which allows the system installer to utilize star, bus, and loop architectures.This controller works in standalone mode, peer-to-peer with one or more other units, or when connected to a Trane Tracer Summit or a 3rd party building automation system that supports LonTalk. The LCI-I controller is available as a factory or field-installed kit.

Return Fan Control

A return fan reduces the load on the supply fan motor or can allow a unit to operate at a higher static pressure.

The return fan VFD is modulated independently to maintain desired return air plenum pressure. In all

Twinning

Twinning is a Master Unit and one, or more, similarly configured Slave Unit(s) operating cooperatively, as a group, to provide higher capacity and/or redundancy at partial capacity.

RT-PRC031-EN

21

Page 21
Image 21
Trane RT-PRC031-EN manual Humidification Control, LonTalk Building Automation System, Return Fan Control, Twinning