Controls VAV and CV

8.Supply Air Static Pressure Setpoint

9.Minimum Outside Air Flow Setpoint

10.Morning Warm Up Setpoint

11.Economizer Dry Bulb Enable Setpoint

12.Supply Air Reheat Setpoint

13.Minimum Outside Air Position Setpoint

14.Occupied Dehumidification Setpoint

15.Unoccupied Dehumidification Setpoint

16.Occupied Humidification Setpoint

17.Unoccupied Humidification Setpoint

Binary Outputs - each of the five (5) relay outputs can be mapped to any/ all of the available diagnostics.

Binary Input - the single binary input can initiate or terminate the Demand Limit mode of operation via a field supplied switch or contact closure.

Generic Building Automation System Module (GBAS 0-10 vdc)

The Generic Building Automation System Module (GBAS 0-10vdc) is used to provide broad control capabilities for building automation systems other than Trane's Tracer™ system. The following inputs and outputs are provided:

Analog Inputs—Four analog inputs, controlled via a field provided potentiometer or a 0-10 vdc signal, that can be configured to be any of the following:

1.Occupied Zone Cooling Setpoint (CV only)

2.Unoccupied Zone Cooling Setpoint (CV only)

3.Occupied Zone Heating Setpoint (CV only)

4.Unoccupied Zone Heating Setpoint (CV only)

5.Supply Air Cooling Setpoint (VAV only)

6.Supply Air Heating Setpoint (VAV only)

7.Space Static Pressure Setpoint

8.Supply Air Static Pressure Setpoint

9.Minimum Outside Air Flow Setpoint

10.Morning Warm Up Setpoint

11.Economizer Dry Bulb Enable Setpoint

12.Supply Air Reheat Setpoint

13.Minimum Outside Air Position Setpoint

14.Occupied Dehumidification Setpoint

15.Unoccupied Dehumidification Setpoint

16.Occupied Humidification Setpoint

17.Unoccupied Humidification Setpoint

Analog Outputs—Four analog outputs that can be configured to be any of the following:

1.Outdoor Air Temperature

2.Zone Temperature

3.Supply Air Temperature (VAV only)

4.Supply Air Pressure (VAV only)

5.Space Pressure

6.Space Relative Humidity

7.Outdoor Air Relative Humidity

8.Space CO2 Level

9.Heat Staging (%)

10.Outdoor Air Damper Position

11.Outdoor Airflow

Binary Output - the single relay output can be mapped to any/all of the available diagnostics.

Binary Input - the single binary input can initiate or terminate the Demand Limit mode of operation, via a field supplied switch or contact closure.

Chilled Water Coil - Freeze Stat

A low limit thermostat, mounted on the entering air side of the coil, is used to help prevent the chilled water coil from freezing during periods of low ambient temperature. If the temperature falls below a predetermined value the low limit

thermostat will trip, the hydronic valve will be fully opened, the supply fan will shut off, and the fresh air dampers will close.

Steam and Hot Water Coil - Freeze Avoidance

Freeze Avoidance is a feature which helps prevent freezing of steam or hot water heat coils during periods of unit inactivity and low ambient temperatures. Whenever the unit supply fan is off, the outdoor air temperature is monitored. If the temperature falls below a predetermined value, the heating valve is opened to a position selected at the unit mounted Human Interface to allow a minimum amount of steam or hot water to flow through the coil and avoid freezing conditions.

Applications with Chilled Water Coil

Occupied/Unoccupied

Switching

Description - 3 ways to switch Occupied/Unoccupied:

1.Night Setback (NSB) Panel

2.Field-supplied contact closure (hard wired binary input to RTM)

3.TRACER (or 3rd Party BAS with LCI module)

Night Setback Sensors

Trane's night setback sensors are programmable with a time clock function that provides communication to the air handler unit through a 2-wire communications link. The desired transition times are programmed at the night setback sensor and communicated to the air handler.

Night setback (unoccupied mode) is operated through the time clock provided in the sensors with night setback. When the time clock switches to night setback operation, the outdoor air dampers close and heating/cooling can be enabled or disabled depending on setup parameters.

As the building load changes, the night setback sensor energizes the air handler heating/cooling (if enabled)

RT-PRC031-EN

19

Page 19
Image 19
Trane RT-PRC031-EN manual Generic Building Automation System Module Gbas 0-10 vdc, Chilled Water Coil Freeze Stat