Installation (Continued)
O/A Sensor & Tubing Installation | Figure |
An Outside Air Pressure Sensor is shipped with all units de- signed to operate on variable air volume applications or constant volume units with 100% modulating exhaust w/ Stratitrac.
On VAV systems, a duct pressure transducer (3U60) and the outside air sensor is used to control the discharge duct static pressure to within a
On CV & VAV units equipped with 100% modulating ex- haust w/Stratitrac, a space pressure transducer (3U62) and the outside air sensor is used to control the exhaust fan and dampers to relieve static pressure, to within a customer- specified parameter, within the controlled space. Refer to Figure
1.Remove the O/A pressure sensor kit located inside the filter section. The kit contains the following items;
O/A static pressure sensor with sensor mounting bracket
2' of 3/16" O.D. pneumatic tubing Mounting hardware
2. Using two
3. Using the
4. Remove the dust cap from the tubing connector located below the sensor in the vertical support.
5. Attach one end of the 2' x 3/16" O.D. factory provided pneumatic tubing to the sensor's top port, and the other end of the tubing to the connector in the vertical support. Discard any excess tubing.
Units with StatitracTM:
6. Open the filter access door, and locate the DSP control devices illustrated in Figure
31