Trane RT-SVX10C-EN specifications Installation Continued, External Auto/Stop Switch 5S67

Models: RT-SVX10C-EN

1 118
Download 118 pages 62.13 Kb
Page 48
Image 48
External Auto/Stop Switch (5S67)

Remote Minimum Position Potentiometer (5U70) (BAYSTAT023A)

The remote minimum position potentiometer is used on units with an economizer. It allows the operator to remotely set the economizer's minimum position (which controls the amount of outside air entering the unit). Use the installation instructions that shipped with the potentiometer to install it, and the appropriate illustrations in Figure 3-16 or

3-17 to connect it to the unit.

External Auto/Stop Switch (5S67)

A field supplied single pole single throw switch (5S67) may be used to shut down the unit operation. This switch is a bi- nary input wired to the RTM. When opened, the unit shuts down immediately and can be cancelled by closing the switch. Refer to the appropriate illustrations in

Figure 3-16 or 3-17 for the proper connection terminals in the unit control panel. The switch must be rated for 12 ma @ 24 VDC minimum.

VOM Contacts (5K90, 5K91, 5K92, 5K93, 5K94)

If the unit is equipped with a Ventilation Override Module (VOM), (i.e. unit model number digit 21+ is a “N”), a num- ber of special functions can be specified by the building owner or contractor. These functions can include, but are not limited to; (1) Unit Off, (2) Pressurization, (3) Exhaust,

(4)Purge, and (5) Purge with Duct Pressure Control. They are controlled by binary inputs wired to the VOM. These functions can be initiated by; a toggle switch, a time clock, or an ICSTM output. The switch must be rated for 12 ma @ 24 VDC minimum. The following preset sequences can be modified by the customer;

1.VOM Mode “A” Priority 1 - Unit Off: -Supply fan - OFF

-Inlet vanes/VFD - 0% (if equipped)

-Exhaust fan - OFF, Exhaust dampers Closed -O/A dampers - Closed

-Heat - All stages OFF, Modulating Heat output at 0 vdc

-Occupied/Unoccupied output - De-energized (Occupied)

-VO Relay - Energized

-Pre-heater State - Off (if equipped)

2.VOM Mode “B” Priority 2 - Pressurize:

-Supply fan - ON

-Inlet Vanes/VFD - 100% (if equipped)

-Exhaust fan - OFF, Exhaust dampers - Closed -O/A dampers - Open

-Heat - All stages OFF, Modulating Heat output at 0 vdc

-Occupied/Unoccupied output - Energized (Unoccupied)

-VO Relay - Energized

-Pre-heater State - Off (if equipped)

3.VOM Mode “C” Priority 3 - Exhaust: -Supply fan - OFF

-Inlet Vanes/VFD - 0% (if equipped)

-Exhaust fan - ON, Exhaust dampers - Open -O/A dampers - Closed

-Heat - All stages OFF, Modulating Heat output at 0 vdc

-Occupied/Unoccupied output - De-energized (Occupied)

-VO Relay - Energized

-Pre-heater State - Off (if equipped)

Installation (Continued)

4.VOM Mode “D” Priority 4 - Purge: -Supply fan - ON

-Inlet Vanes/VFD - 100% (if equipped)

-Exhaust fan - ON, Exhaust dampers - Open -O/A dampers - Open

-Heat - All stages OFF, Modulating Heat output at 0 vdc

-Occupied/Unoccupied output - Energized (Unoccupied)

-VO Relay - Energized

-Pre-heater State - Off (if equipped)

5.VOM Mode “E” Priority 5 - Purge with duct pressure control:

-Supply fan - ON

-Inlet Vanes/VFD - (if equipped) Controlled by

S/A Pressure Control with supply air pressure high limit disabled.

-Exhaust fan - ON, Exhaust dampers - Open -O/A dampers - Open

-Heat - All stages OFF, Modulating Heat output at 0 vdc

-Occupied/Unoccupied output - Energized (Unoccupied)

-VO Relay - Energized

-Pre-heater State - Off (if equipped)

"OFF" - will appear in the Ventilation Override screen after all VOM binary inputs have been reset (opened).

Due to codes in some areas, the definitions for some or all of the VOM modes may have to be locked into the program by the user. Once the definitions are locked, the Ventilation Override Module must be replaced in order to reprogram that sequence.

Refer to Figure 3-16 & 3-17 for the proper connection termi- nals in the unit control panel for each of the VOM initiating device’s and the appropriate Programming, Troubleshooting Guide (PTG Latest Edition) for programming instructions.

Emergency Override Definitions (with LCI-I module installed)

When an LCI-I module is installed, the user can initiate one of five (5) Emergency Override sqeuences that have the fol- lowing predefined unit operation:

PRESSURIZE

Supply Fan - On

Inlet Vanes - Open (if equipped) Exhaust Fan - Off (if equipped)

Exhaust Dampers - Closed (if equipped) OA Dampers - Open

Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output - Energized

VO Relay - Energized (with VOM module installed) OA Preheater State - Off (with VCM module installed)

DEPRESSURIZE

Supply Fan - Off

Inlet Vanes - Closed (if equipped) Exhaust Fan - On (if equipped) Exhaust Dampers -Open (if equipped) OA Dampers - Closed

Heat - All heat stages Off (staged gas and elec.), Hydronic heat & Mod Gas Heat output at 0%. Occupied/Unoccupied output - De-energized

VO Relay - Energized (with VOM module installed) OA Preheater State - Off (with VCM module installed)

47

Page 48
Image 48
Trane RT-SVX10C-EN specifications Installation Continued, External Auto/Stop Switch 5S67