Installation (Continued)

Table 3-3

Typical Unit & Curb Weights

 

 

Typical Unit Operating Weight (1)

 

Roof Curb

Unit

 

SE,SL,

 

 

 

 

 

Max. Weight (3)

Size

SAHF

SSHF

SFHF

SXHF

SEHG

SFHG

SXHG

SAHF

S*HF/G

C20

4360

4690

4970

4580

 

 

 

490

510

C25

4520

4860

5130

4750

 

 

 

490

510

C30

5220

5590

5840

5460

 

 

 

490

510

C40

6890

7400

7880

7240

 

 

 

515

550

C50

7890

8450

8900

8290

 

 

 

515

550

C55

8140

8690

9170

8540

 

 

 

515

550

C60

9320

9650

10120

9480

 

 

 

610

640

C70

9860

10160

10640

10040

 

 

 

610

640

C75

9860

10160

10640

10040

 

 

 

610

640

C90

 

 

 

 

14730

15400

14580

 

770

D11

 

 

 

 

15310

15940

15160

 

770

D12

 

 

 

 

15730

16370

15560

 

770

D13

 

 

 

 

16080

16710

15930

 

770

 

 

Typical Unit Operating Weight (2)

 

Roof Curb

Unit

 

SE,SL,

 

 

 

 

 

Max. Weight (3)

Size

SAHF

SSHF

SFHF

SXHF

SEHG

SFHG

SXHG

SAHF

S*HF/G

C20

4650

5000

5270

4860

 

 

 

490

510

C25

4830

5180

5440

5060

 

 

 

490

510

C30

5570

5930

6200

5800

 

 

 

490

510

C40

7290

7820

8280

7650

 

 

 

515

550

C50

8350

8900

9380

8740

 

 

 

515

550

C55

8600

9160

9640

9010

 

 

 

515

550

C60

9840

10150

10620

10010

 

 

 

610

640

C70

10370

10690

11160

10560

 

 

 

610

640

C75

10370

10690

11160

10560

 

 

 

610

640

C90

 

 

 

 

15460

16050

15240

 

770

D11

 

 

 

 

15950

16590

15810

 

770

D12

 

 

 

 

16380

17010

16220

 

770

D13

 

 

 

 

16730

17380

16580

 

770

Note: 1. The weights shown in this table represents the typical unit operating weights for the heating/cooling function indicated with an economizer and exhaust fan installed.

2.The weights shown represents the typical unit operating weights for the heating/cooling function indicated with an economizer, exhaust fan with supply & exhaust VFD installed.

3.Roof curb weights include the curb and pedestal.

Roof Curb and Ductwork

The roof curbs for 20 through 130 Ton units consists of two main components; a pedestal to support the unit’s con- denser section and a "full perimeter" enclosure to support the unit’s air handler section.

Before installing any roof curb, verify;

1.That it is the correct curb for the unit,

2.That it includes the necessary gaskets and hardware,

3.That the purposed installation location provides the required clearance for proper operation.

4.Insure that the curb is level and square. The top surface of the curb must be true to assure an adequate curb-to-unit seal.

Step-by-step curb assembly and installation instructions ship with each Trane accessory roof curb kit. Follow the in- structions carefully to assure proper fit-up when the unit is set into place.

Note: To assure proper condensate flow during operation, the unit (and curb) must be as level as possible. The maximum slope allowable for rooftop unit applications, excluding SSH_'s, is 4" end-to- end and 2" side-to-side. Units with steam coils (SSH_'s) must be set level!

If the unit is elevated, a field constructed catwalk around the unit is strongly recommended to provide easy access for unit maintenance and service.

Recommendations for installing the Supply Air and Return Air ductwork joining the roof curb are included in the curb instruction booklet. Curb ductwork must be fabricated and installed by the installing contractor before the unit is set into place.

Note: For sound consideration, cut only the holes in the roof deck for the ductwork penetrations. Do not cut out the entire roof deck within the curb perimeter.

22

Page 23
Image 23
Trane RT-SVX10C-EN specifications Roof Curb and Ductwork, Se,Sl, Sahf Sshf Sfhf Sxhf Sehg Sfhg Sxhg HF/G