Figure 3-10 (Continued)

Unit Gas Trains (Natural Gas)

1000 MBH

Modulating (500 MBH - 1000 MBH)

Flue Assembly Installation

1.Locate the flue assembly and the extension (refer to Fig- ure 3-11 for extension usage) in the shipwith section of the unit.

2.Install the flue extension onto the flue assembly as shown in Figure 3-11.

3.Slide the pipe clamp onto the heater flue tube located in- side the heater compartment.

Installation (Continued)

4.Insert the tube on the flue assembly into the hole located in the vertical support for the heat section.

5.Butt both flue tube sections together and center the pipe clamp over joint.

6.Using the pre-punch holes in the flue assembly, exten- sion, and the vertical support, install the appropriate number of mounting brackets. Refer to Figure 3-11 for details.

Figure 3-11

Flue Assembly

Hot Water Heat Units (SLH_)

Hot water heating coils are factory installed inside the heater section of the unit. Once the unit is set into place, the hot water piping and the factory provided three way modulating valve must be installed. The valve can be in- stalled inside the heat section or near the unit. If the valve is installed in a remote location, use field supplied wiring to extend the control wires from the heater section to the valve. Two access holes are provided in the unit base as il- lustrated in Figure 3-2.

Following the guidelines listed below will enchance both the installation and operation of the "wet heat" system.

Figure 3-12 illustrates the recommended piping configura- tion for the hot water coil. Table 3-5 list the coil connection sizes.

Note: The valve actuators are not waterproof. Failure to protect the valve from moisture may result in the loss of heating control.

1.Support all field-installed piping independently from the heating coil.

2.Use swing joints or flexible connectors adjacent to the heating coil. (These devices will absorb the strains of ex- pansion and contraction).

3.All return lines and fittings must be equal to the diameter of the "outlet" connection on the hot water coil.

34

Page 35
Image 35
Trane RT-SVX10C-EN specifications MBH Modulating 500 MBH 1000 MBH, Hot Water Heat Units SLH, Flue Assembly Installation