Table 4-7

Recommended Manifold Pressures and CO2 Levels during Furnace Operation (See Notes)

Furnace

MBH

Firing

Manifold

Stage

 

Rate

%CO2

Pressure

High-Fire

235

100%

8.5-9.5

3.0-3.5

Low-Fire

117

50%

6.0-7.0

0.9

High-Fire

350

100%

8.5-9.5

3.0-3.5

Low-Fire

175

50%

6.0-7.0

0.9

High-Fire

500

100%

8.5-9.5

3.0-3.5

Low-Fire

250

50%

6.0-7.0

1.25

High-Fire

850

100%

8.5-9.5

3.0-3.5

Low-Fire

500

59%

6.0-7.0

1.25

High-Fire

1000

100%

8.5-9.5

3.0-3.5

Low-Fire

500

50%

6.0-7.0

1.25

Manifold pressures are given in inches w.c.

High fire manifold pressure is adjustable on all heaters. Low fire manifold pressure is non-adjustable on 235 MBH and 350 MBH heaters.

Figure 4-7

Flue Gas Carbon Dioxide & Oxygen Measurements

Table 4-8

Natural Gas Combustion Curve

(Ratio of Oxygen to Carbon Dioxide in percent)

Percent Carbon Dioxide

18

 

 

 

 

 

 

 

 

 

 

 

 

17

 

 

 

 

 

 

 

 

 

Curve

 

Fuel

16

 

 

 

 

 

 

 

 

 

A

=

1,000 BTU per cu. ft.

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of Natural Gas.

14

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

A

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

0

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15 16 17 18 19 20 21

 

 

 

 

 

 

 

 

Percent Oxygen

 

Figure 4-8

Gas Valve Adjustment Screw Locations

96

Page 98
Image 98
Trane RT-SVX10C-EN specifications Mbh, Firing Manifold, CO2 Pressure