Table 4-1 (Continued)

Service Test Guide for Component Operation

COMPONENT

 

 

 

 

COMPONENT CONFIGURATION

 

 

 

 

 

Occ

BEING TESTED

Supply

Exhaust

Condenser

Heat Stages

 

Compressor Stage

 

Econo

Exhaust

 

VFD

Unocc

(Cont.)

Fan

Fan

Fans

1

2

3

1

2

3

 

4

Damper

Damper

IGV

Output

Relay

** CONDENSER FANS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90 Ton

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1A-2B3/2B14

Off

Off

1A-On/1B-Off

Off

Off

Off

K11-Off

K3-Off

K12-On

K4-Off

Closed

Closed

Closed

0%

Default

 

 

 

2A-Off/2B-Off

 

 

 

 

 

 

 

 

 

 

 

 

 

1B-2B1/2B2

Off

Off

1A-Off/1B-On

Off

Off

Off

K11-On

K3-Off

K12-Off

K4-Off

Closed

Closed

Closed

0%

Default

 

 

 

2A-Off/2B-Off

 

 

 

 

 

 

 

 

 

 

 

 

 

2A-2B6/2B13

Off

Off

1A-Off/1B-Off

Off

Off

Off

K11-Off

K3-Off

K12-Off

K4-On

Closed

Closed

Closed

0%

Default

 

 

 

2A-On/2B-Off

 

 

 

 

 

 

 

 

 

 

 

 

 

2B-2B4/2B5

Off

Off

1A-Off/1B-Off

Off

Off

Off

K11-Off

K3-On

K12-Off

K4-Off

Closed

Closed

Closed

0%

Default

105 & 115 Ton

 

 

2A-Off/2B-On

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1A-2B3/2B14

Off

Off

1A-On/1B-Off

Off

Off

Off

K11-Off

K3-Off

K12-On

K4-Off

Closed

Closed

Closed

0%

Default

 

 

 

2A-Off/2B-Off

 

 

 

 

 

 

 

 

 

 

 

 

 

1B-2B1/2B2/2B19

Off

Off

1A-Off/1B-On

Off

Off

Off

K11-On

K3-Off

K12-Off

K4-Off

Closed

Closed

Closed

0%

Default

 

 

 

2A-Off/2B-Off

 

 

 

 

 

 

 

 

 

 

 

 

 

2A-2B6/2B13

Off

Off

1A-Off/1B-Off

Off

Off

Off

K11-Off

K3-Off

K12-Off

K4-On

Closed

Closed

Closed

0%

Default

 

 

 

2A-On/2B-Off

 

 

 

 

 

 

 

 

 

 

 

 

 

2B-2B4/2B5/2B15

Off

Off

1A-Off/1B-Off

Off

Off

Off

K11-Off

K3-On

K12-Off

K4-Off

Closed

Closed

Closed

0%

Default

130 Ton

 

 

2A-Off/2B-On

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1A-2B3/2B14

Off

Off

1A-On/1B-Off

Off

Off

Off

Off

Off

Off

 

Off

Closed

Closed

Closed

0%

Default

 

 

 

2A-Off/2B-Off

 

 

 

 

 

 

 

 

 

 

 

 

 

1B-2B1/2B2

Off

Off

1A-Off/1B-On

Off

Off

Off

Off

Off

Off

 

Off

Closed

Closed

Closed

0%

Default

2B19/2B20

 

 

2A-Off/2B-Off

 

 

 

 

 

 

 

 

 

 

 

 

 

2A-2B6/2B13

Off

Off

1A-Off/1B-Off

Off

Off

Off

Off

Off

Off

 

Off

Closed

Closed

Closed

0%

Default

 

 

 

2A-On/2B-Off

 

 

 

 

 

 

 

 

 

 

 

 

 

2B-2B4/2B5

Off

Off

1A-Off/1B-Off

Off

Off

Off

Off

Off

Off

 

Off

Closed

Closed

Closed

0%

Default

2B15/2B21

 

 

2A-Off/2B-On

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLY FAN

On

Off

All Off

Off

Off

Off

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

EXHAUST FAN

Off

On

All Off

Off

Off

Off

Off

Off

Off

 

Off

Closed

100%

100%

100%

Default

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

Open

 

 

GAS HEAT (Full Cap.)

On

Off

All Off

On

On

N/A

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

Stage 1

On

Off

All Off

On

Off

N/A

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

Stage 2

On

Off

All Off

Off

On

N/A

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

Full Modulating

On

Off

All Off

90% Select

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

(High Fire Adjustment)

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

Full Modulating

On

Off

All Off

5% Select

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

(Low Fire Adjustment)

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

Limited Modulating

On

Off

All Off

90% Select

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

(High Fire Adjustment)

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

Limited Modulating

On

Off

All Off

33% Select

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

(Low Fire Adjustment)

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

ELECTRIC HEAT

On

Off

All Off

On

On

On

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

Stage 1

On

Off

All Off

On

Off

Off

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

Stage 2

On

Off

All Off

Off

On

Off

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

Stage 3

On

Off

All Off

Off

Off

On

Off

Off

Off

 

Off

Closed

Closed

100%

100%

Unocc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

Hydronic Heat

Off

Off

All Off

100% Select

Off

Off

Off

 

Off

Closed

Closed

Closed

0%

Default

Pre - Heater

Off

Off

All Off

On

N/A

N/A

Off

Off

Off

 

Off

Closed

Closed

Closed

0%

Default

Fresh Air Dampers

Off

Off

All Off

Off

Off

Off

Off

Off

Off

 

Off

100%

Closed

Closed

0%

Default

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

 

 

Exhaust Dampers

Off

Off

All Off

Off

Off

Off

Off

Off

Off

 

Off

100%

100%

Closed

0%

Default

 

 

 

 

 

 

 

 

 

 

 

 

 

Open

 

 

 

*- Compressors for the 20 thru 60 Ton units can operate individually or together and in any order while in the SERVICE TEST mode. Compressors 1A &1B and compressors 2A & 2B operate simultaneously within their respective circuits on the 70 thru 105 Ton units. Compressors 1A & 1B, 1C & 1D, 2A & 2B, 2C & 2D operate simultaneously within their respective circuits on 115 and 130 Ton units.

Caution: Do Not operate the compressors for extended periods of time without the condenser fans, High Head Pressure will develope.

**- Condenser fan outputs can operate individually or together and in any order while in the SERVICE TEST mode.

***- Once the unit has started, refer to the Status Menu in the Human Interface for the OA CFM.

****- RTM OCC/UNOCC output in the Service Test Mode must be in the unoccupied mode to open the system VAV boxes and the Inlet Guide Vanes or to drive the VFD to 100%.