Service & Maintenance (Continued)

Table 5-4

Filter Data

 

Panel-Type Filters

Bag-Type Filters

Cartridge Filters

Panel-Type Prefilters

Unit Model

 

(Note 1)

 

(Note 2)

(box-type) (Note 2)

 

(Note 3)

 

Qty

Size of each

Qty.

Size of each

Qty.

Size of each

Qty.

Size of each

S_HF-C20 &

12

20 X 20 X 2

4

12 X 24 X 19

4

12 X 24 X 12

4

12 X 24 X 2

C25

 

 

3

24 X 24 X 19

3

24 X 24 X 12

3

24 X 24 X 2

S_HF-C30

16

20 X 20 X 2

2

12 X 24 X 19

2

12 X 24 X 12

2

12 X 24 X 2

 

 

 

6

24 X 24 X 19

6

24 X 24 X 12

6

24 X 24 X 2

S_HF-C40

16

20 X 25 X 2

5

12 X 24 X 19

5

12 X 24 X 12

5

12 X 24 X 2

 

 

 

6

24 X 24 X 19

6

24 X 24 X 12

6

24 X 24 X 2

S_HF-C50 &

20

20 X 25 X 2

3

12 X 24 X 19

3

12 X 24 X 12

3

12 X 24 X 2

C55

 

 

9

24 X 24 X 19

9

24 X 24 X 12

9

24 X 24 X 2

S_HF-C60,

35

16 X 20 X 2

6

12 X 24 X 19

6

12 X 24 X 12

6

12 X 24 X 2

C70 & C75

 

 

8

24 X 24 X 19

8

24 X 24 X 12

8

24 X 24 X 2

S_HG-C90 &

25

24 X 24 X 2

3

12 X 24 X 19

3

12 X 24 X 12

3

20 X 24 X 2

S_HG-D11

 

 

15

24 X 24 X 19

15

24 X 24 X 12

15

24 X 24 X 2

S_HG-D12 &

25

24 X 24 X 2

3

12 X 24 X 19

3

12 X 24 X 12

3

20 X 24 X 2

S_HG-D13

 

 

15

24 X 24 X 19

15 24 X 24 X 12

15

24 X 24 X 2

Notes:

 

 

 

 

 

 

 

 

1.Dimensions shown for “Panel-Type Filters”apply to “Throw away”, “Cleanable Wire Mesh”, and “High Efficiency Throw away” Filters.

2.S_HF units ordered with “Bag-Type Filters” or “Cartridge Filters” (box-type) include a bank of “Panel-Type Prefilters”.

3.The same “Panel-Type Prefilters” are used with “Bag-Type” and “Cartridge (box-type)” filters.

Table 5-5

"Wet Heat" Coil Fin Data

 

 

 

Total Coil

Fins

Fins

 

Coil

Coil

Face Area

per

per

Model

Type

Rows

(sq.ft.)

Foot

Foot

SLHF-C20,

WC

 

 

 

 

C25 & C30

Prima Flo

2

13.75

80

110

 

(hot water)

 

 

 

 

SLHF-C40,

WC

 

 

 

 

C50 & C55

Prima Flo

2

19.25

80

110

 

(hot water)

 

 

 

 

SLHF-C60,

WC

 

 

 

 

C70 & C75

Prima Flo

2

26.25

80

110

 

(hot water)

 

 

 

 

SLHG-C90,

WC

 

 

 

 

D11, D12

Prima Flo

2

17.5 (2)

80

110

& D13

(hot water)

 

 

 

 

SSHF-C20,

NS

1

13.75

42

96

C25 & C30

(steam)

 

 

 

 

SSHF-C40,

NS

1

13.75 (1)

42

96

C50 & C55

(steam)

 

5.5 (1)

 

 

SSHF-C60,

NS

1

18.75 (1)

42

72

C70 & C75

(steam)

 

7.5 (1)

 

 

SLHG-C90,

NS

1

17.5 (2)

52

96

D11, D12

(steam)

 

 

 

 

& D13

 

 

 

 

 

Note: To determine unit heating capacity (i.e., “low heat” or “hi gh heat”), see Digit 9 of the model number stamped on the unit nameplate.

102

Page 104
Image 104
Trane RT-SVX10C-EN Unit Model Box-type Note Qty, Qty Size of each, Wet Heat Coil Fin Data Total Coil Fins, Model Type