8 – Communications

8 – Communications

Note: These connections are optional. The UPS system will function without these connections.

8-1 Network Card

The UPS system includes an internal network card that provides an Ethernet interface for remote monitoring and control of the UPS system. Refer to the network card documentation for additional information. Note: The network card must be removed in order to use the UPS system’s RS-232 port.

8-2 EPO Connection

Shorting the EPO terminals activates the EPO (emergency power off) function, which provides emergency shutdown of the UPS system.

8-3 RS-232 Serial Communications

Note: The network card must be removed in order to use the UPS system’s RS-232 port.

Use the included RS-232 (DB9) serial cable to connect the UPS system’s RS-232 serial port to a computer’s RS-232 serial port. Install the included software on the computer in order to monitor and control the UPS system. (See the software documentation for system requirements, installation instructions and additional information.)

RS-232 interface settings:

Baud Rate

2400 bps

 

 

Data Length

8 bits

 

 

Stop Bit

1 bit

 

 

Parity

None

 

 

RS-232 pin assignments:

9

8

7

6

5

4

3

2

1

Pin 3: RS-232 Rx

Pin 2: RS-232 Tx

Pin 5: Ground