10 – Specifications

10 – Specifications

Input

 

 

 

 

 

 

 

Voltage Range

Up to 160-280/277-485V AC (3Ø, 4-Wire + Ground, Wye)

 

(160-176/277-305V AC at Load < 75%)

 

 

 

 

Frequency Range

45 to 65 Hz

 

 

 

 

Power Factor

Up to 0.99 at 100% Linear Load

Output

 

 

 

 

 

 

 

Voltage Range

User-Selectable 200/220/230/240V AC (1Ø, 2-Wire + Ground)

 

 

 

 

Voltage Adjustment

±0%; ±1%; ±2%; ±3%

 

 

 

 

Voltage Regulation

±2%

 

 

 

 

Capacity

10 kVA / 7 kW

 

 

 

 

Rated Power Factor

0.8 Lagging

 

 

 

 

Wave Form

Pure Sine Wave, THD <3%

 

 

 

 

Frequency Stability

±0.2% (Free-Running)

 

 

 

 

Frequency Regulation

±1%; ±3%

 

 

 

 

Transfer Time to Battery

0 ms

 

 

 

 

Crest Factor

3:1 Acceptable

 

 

 

 

Efficiency (AC to AC, Normal Mode)

Up to 91%

 

 

 

 

Efficiency (AC to AC, Economy Mode)

Up to 93%

 

 

 

 

Estimated Full Load Runtime

 

 

5 minutes

 

 

 

 

Estimated Half Load Runtime

 

 

14 minutes

 

 

 

 

Physical

 

 

 

 

 

 

 

Dimensions (H x W x D)

135 x 440 x 680 mm (Power Module)

 

 

 

 

Input/Output Connection

Hardwire

 

 

 

 

Unit Weight

28 kg (Power Module)

 

 

 

 

11 – Storage and Service

Storage

First turn the UPS system’s output and utility input breaker OFF, then disconnect the UPS system’s input from the AC utility power source. Next, disconnect all equipment. The UPS system must be stored in a clean, secure environment with a temperature less than 40° C and a relative humidity less than 90% (non-condensing). Note: If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 12-hour period every three months in moderate-temperature environments (-15° to 30° C), or every two months in high- temperature environments (30° to 40° C). Failure to recharge the batteries periodically may cause irreversible battery damage.

Service

The UPS system is covered by the limited warranty described in this manual. Extended and on-site warranty options are also available. For more information, call Tripp Lite Customer Service at +1.773.869.1234. If returning the UPS system to Tripp Lite, carefully pack the UPS system using the original packing material that came with the unit. Enclose a letter describing the symptoms of the problem. If the UPS system is within the warranty period, enclose a copy of the sales receipt.