9 – Troubleshooting

If the UPS system malfunctions during operation, check the following:

Is the input and output wiring correct?

Is the utility AC input voltage within the acceptable range for the UPS system?

If problems persists, please refer to the instructions below. If the problem continues to persist after following the instructions below and/or restarting the UPS system, contact Tripp Lite for service.

Problem

LCD Screen Error Code

Possible Solution

 

 

 

 

Fault LED

Er05 +

+

Check the battery connection, then recharge the battery for 12 hours. If the

 

 

 

problem persists, contact Tripp Lite for service and/or battery replacement.

 

 

 

Fault LED

Er06/Er10/Er12/Er28 +

If the breaker has tripped, turn off the UPS system completely and allow

 

 

 

it to cool. Remove some of the load from the UPS output, then reset the

 

 

 

breaker and restart the UPS. If any of the wiring appears to be damaged,

 

 

 

replace it.

 

 

 

 

Fault LED

EPO

 

Remove the EPO terminal short circuit.

 

 

 

 

Fault LED

Er11/Er33

 

Remove any objects blocking the ventilation holes. Make sure the UPS

 

 

 

location provides adequate ventilation.

 

 

 

 

Fault LED

Er14

 

Check the cooling fans on the rear panel. If the problem persists, contact

 

 

 

Tripp Lite for service.

 

 

 

 

Fault LED

Er15

 

Make sure the UPS is operating in normal mode. If it is operating in CVCF

 

 

 

mode, restart the UPS.

 

 

 

 

Fault LED

Er16/Er27

 

All parallel UPS parameters except ID number must be same. Adjust the

 

 

 

parameters.

 

 

 

 

Fault LED

Er21

 

Reconnect the RJ45 cable or set a UPS with ID=1.

 

 

 

Fault LED

Other Error Code

Have a qualified electrician check the AC supply circuit and wiring, then

 

 

 

restart the UPS system. If the problem persists, contact Tripp Lite for

 

 

 

service.

 

 

 

UPS fails to offer battery

Not Applicable

Recharge the battery uninterrupted for 12 hours. If the problem persists,

backup or backup time is

 

 

contact Tripp Lite for service and/or battery replacement.

much shorter than calculated.

 

 

 

 

 

 

UPS locks itself and cannot

Not Applicable

Attempt to restart the UPS system (see below). If the problem persists,

be turned off.

 

 

contact Tripp Lite for service.

 

 

 

 

UPS Detects Error While in Self-Test Mode

If a serious abnormal condition occurs, the UPS system will lock itself in the “OFF” position AAA and the fault LED will illuminate on the

control panel. After three seconds, all messages will be locked except for bypass messages ( and). If the AC utility input power

becomes abnormal after the UPS locks, the LED will go out and will appear on the LCD.

To release the UPS system lock:

1.Troubleshoot the UPS system problem using the chart above.

2.Press the “OFF”button for five seconds until the buzzer sounds twice, then release the button.

3.Turn off the utility input breaker.

4.Restart the UPS system by following the instructions in Section 6-3 – Normal Mode Startup.

5.If the problem persists, contact Tripp Lite for service.