VENTING INSTALLATION

INSTALLATION OF LISTED B-1 VENTINSTALLING VENT SYSTEM IN A CHASECHECKING VENT CAPACITYManual background® SBVBN(C) AND SBVBP(C)

CAST IRON STOVE AND BURNER SYSTEM

VENTING INSTALLATION

Continued

INSTALLATION OF LISTED B-1 VENT

Manual backgroundWARNING: Installation should only be made by qualified per- sons who are familiar with the safety procedures required for the installation of the product, who are equipped with the proper tools and testing instruments, and who have achieved proper certification of licensing. Instal- lations made by unqualified per- sons can result in the risk of in- jury or electrical shock which can be serious or even fatal.

Figures 22 through 24 show other options for the gas vent. When venting through a side wall your vent pipe must have the proper temperature rating (see Figure 24). Manufacturer's clearances must also be maintained. Consult the authority having jurisdiction in your area regarding venting through side wall.

Figure 23 - Vertical Venting Configuration Through Chimney

INSTALLING VENT SYSTEM IN A CHASE

A chase is a vertical box-like structure built to enclose venting that runs along the out- side of a building. A chase is not required for such venting.

NOTICE: Treatment of firestops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the re- quirements of local building codes. You must follow all local building codes.

Note: When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially im- portant in cold climates. Minimum clear- ance between vent pipes and combustible materials such as insulation is 1".

CHECKING VENT CAPACITY

Complete all gas piping, electrical, and vent connections. After adjusting the burner sys- tem and lighting the main burners, allow a couple of minutes for warm-up. Hold a lighted match just under the rim of the draft hood relief opening. Proper venting will draw the flame toward or into the draft hood. Improper venting, indicated by escape or spillage of burned gas, will cause match to flicker or go out. Smoke from a cigarette will also be pulled into the draft hood if the vent is drawing properly.

Figure 24 - Venting Through a Side Wall

Figure 22 - Vertical Venting Through

Ceiling Using Two 90º Elbows

Figure 25 - Test for Proper Venting