Side Wall Termination Assembly

Vermont Castings Jefferson Direct Vent/Natural Vent Gas Heater

ST356

Fig. 21 Simpson Dura-Vent - install outer adapter pipe.

Side Wall Termination Assembly

1.Locate the vent opening on the wall. Refer to Figure 5, Page 6, to determine the opening centerline. It may be necessary to first position the stove and measure to find the hole location. Depending on whether the wall is made of combustible materials, cut the opening to the size shown in Figure 22. Combustible wall openings must be framed as shown in Figure 22.

CFM System

9³⁄₈Ó

 

(240mm)

 

9³⁄₈Ó

 

 

(240mm)

 

 

Combustible Wall

 

DuraVent

10Ó

Framing Detail

System

(254mm)

 

 

10Ó

 

7¹⁄₂Ó

(254mm)

 

 

VO584-100

 

Noncombustible Wall

 

 

Fig. 22 Locate vent opening.

2.Measure the wall thickness and cut the wall sleeve sections to proper length (MAXIMUM 12Ó). Assemble the sleeve with the #8 sheet metal screws supplied. Attach the firestop plate to the sleeve end with the holes. (Fig. 23) NOTE: The wall sleeve is required in combustible walls only.

3.Install the Wall Firestop/Sleeve assembly into the wall cutout and fasten the firestop to the wall cutout framing members. (Fig. 23)

12Ó

 

(305mm)

Sleeve

Max. Length

 

#8 Sheet

 

Metal Screws

 

Firestop

 

ZCS103

Fig. 23 Assemble the wall sleeve and firestop.

For DuraVent pipe only: Install vent pipe by aligning the locking system together, sliding the pipes together and twisting clockwise.

Install 90° elbow. Twist lock as before.

Slide the wall plate over horizontal run before attaching the horizontal run to the elbow. Fasten wall plate to wall.

4.For CFM Vent Pipe only: If necessary, measure to determine the vertical length (X) of pipe required from the adapter pipe to the wall cutout centerline, including a 2Ó overlap at the joint. (Fig. 24) use a hacksaw or tin snips to trim the pipe as needed.

X

ST214

Fig. 24 Determine the vertical pipe length.

5.Install first the inner then the outer straight pipe section(s), trimmed end down, to the point of the elbow. Drill 3 holes through each joint and fasten with sheet metal screws.

16

20002191

Page 16
Image 16