Initial Power-Up

Initial Power-Up

Power Up

Turn on AC power to the system. The thermostat will automatically identify the communicating components installed.

Messages at Thermostat

During power up, the thermostat will scroll the word “SEARCHING” in the message area, indicating that the system is looking for components (Air Handler, Furnace, Heat Pump, Air Conditioner) on the Climate Talk network. Once the components are identified the message display will indicate the components found. Confirmation will be given in the message area that the equipment has been found with the message

(equipment) FOUND.

Note: If the thermostat display continuously shows “SEARCHING”, check the wiring to the thermostat.

Communications Systems

The thermostat will recognize the system devices that are connected and the capacities to set the system up to the operating settings. The system has additional flexibility which allows for the customization of certain parameters.

 

 

Advanced Installer Configuration Menu

Heat Pump User Menus (Cont.)

 

 

 

 

 

Cool Setup

 

 

 

 

Parameter

Options

 

Comments

 

 

 

 

 

 

AC Profile

A, B, C, D

 

Selectable Airflow Profiles (see Heat Pump

 

 

 

 

Installer Guide)

 

 

 

 

 

 

Cool Air Adj %

-10, 0, 10

 

Selectable Cooling Airflow Adjustments

 

 

 

 

 

 

On Demand

On, Off

 

Select Blower Operation on based on

 

Dehum

 

 

humidity

 

 

 

 

 

 

Reset All Dflts

No, Yes

 

Resets the Heat Pump to the Factory

 

 

 

 

Default Configuration by selecting Yes

 

 

 

 

 

 

 

 

 

 

 

Heat Setup

 

 

 

 

Parameter

Options

 

Comments

 

 

 

 

 

 

HP Profile

A, B, C, D,

 

Selectable Airflow Profiles (See Heat Pump

 

 

 

 

Installer Guide)

 

 

 

 

 

 

Heat Air Adj %

-10, 0, 10

 

Selectable Heat Pump Airflow Adjustments

 

 

 

 

 

 

Dfrost Cmpr Dly

0, 5,

 

Selectable Compressor Delay during

 

 

 

 

defrost

 

 

 

 

 

 

Reset All Dflts

No, Yes

 

Resets the Heat Pump to the Factory

 

 

 

 

Default Configuration by selecting Yes

 

 

 

 

 

 

HP Staging

On, Off

 

For Multi-Stage Heat Pumps Factory

 

(Multi-Stage Units

 

 

Default is On. This allows Low/High stages

 

Only)

 

 

of capacities. To only allow High capacity in

 

 

 

 

Heat Pump Mode select Off

 

 

 

 

 

 