Thermostat Setup
Set Up Thermostat Options
The Thermostat has options that can be selected and adjusted. These options are in the Thermostat Options Configuration Menu. On the Home Screen Display, touch the Menu key to display additional key choices.
Touch and hold the Installer Config key for 3 seconds. This displays the first menu item as shown in the next step. Touch or to change a menu option. Touchto advance to the next menu item orto return to the previous menu item. Touch Run Schedule at any time to exit the menu and return to Home Screen Display.
| Select On Demand Dehumidification |
| (ODD) setting. Default is OFF. It can |
| be set in the range of 40 to 94%. Above |
1 | 94% is the OFF setting. Ideally, the |
2 | indoor humidity should be set in the |
| range of 40 to 60%. |
When On Demand Dehumidification is selected, the thermostat will indicate the current humidity on the home screen. The display will show RH with the humidity %. If the current humidity is above the selected setting, the thermostat will send an On Demand Dehumidification request.
On Demand Dehumidification improves the comfort level in your home by reducing the humidity level. This is accomplished by slowing down the system fan speed and lengthening the run time. The humidity setting may not be reached before the call for cool has been satisfied as the system priority is to maintain the temperature in the home.
Advanced Installer Configuration Menu
Air Handler User Menus
Status
Parameter | Indications | Comments |
|
|
|
Auxiliary Heat | On, Off | Auxiliary Heat Status |
|
|
|
Blower CFM | CFMXXXX | Air Handler Blower CFM |
|
|
|
Motor Mfgr | Rgblt, Emerson | Blower Motor Manufacturer |
|
|
|
Motor RPM | RPMXXXX | Blower Motor RPM |
|
|
|
Maximum CFM | CFMXXXX | Maximum CFM of the Air Handler |
|
|
|
Temp Rise | NA, XXXF, FLT | Difference Between the Supply and |
|
| Return Air Temperature (NA if either |
|
| sensor is disabled) |
|
|
|
Return Temp | NA (if disabled), | Displays Return Air Temperature |
| XXXF, FLT | (if installed and enabled in Setup) |
|
|
|
Supply Temp | NA (if disabled), | Displays Supply Air Temperature |
| XXXF, FLT | (if installed and enabled in Setup) |
|
|
|
|
|
|
2 Week History (2 WK HIST) |
| |
Parameter | Indications | Comments |
|
|
|
2wk AuxHT Hrs | XXX | 2 Week Auxiliary Heat Hours of Operation |
|
|
|
2wk AuxHT Cycls | XXXX | 2 Week Auxiliary Heat Cycles |
|
|
|
2wk G Hrs | XXX | 2 Week Blower Hours of Operation |
|
|
|
2wk G Cycles | XXXX | 2 Week Blower Cycles |
|
|
|
|
| |
Life History (LIFE HIST) |
| |
Parameter | Indications | Comments |
|
|
|
Total Days Pwrd | XXXX | Total number of days control has been |
|
| powered |
|
|
|
Aux HT Hrs | XXXXXX | Auxiliary Heat Hours of Operation |
|
|
|
Aux HT Cycles | XXXXXX | Auxiliary Heat Cycles |
|
|
|
G Hrs | XXXXXX | Continuous Fan Hours of Operation |
|
|
|
G Cycles | XXXXXX | Continuous Fan Cycles |
|
|
|