Thermostat Setup
Advanced Installer Configuration Menu |
1
2
1
2
Select UV lamp maintenance
reminder. Scrolling message will show “UV LAMP MAINTENANCE”. Default is OFF. It can be changed to a setting from 25 to 1975 days in increments of 25 days to select the amount of time for the reminder. Setting of 350 days is an annual reminder.
Based on this setting, the scrolling message area will show “CHANGE UV LAMP” to indicate maintenance is required.
Select humidifier pad maintenance
reminder. Scrolling message will show
“HUMIDIFIER PAD MAINTENANCE”. Default is OFF. It can be changed to a setting from 25 to 1975 hours in increments of 25 hours to select the amount of time for the reminder. Setting of 100 hours is typically 6 months of run time.
Based on this setting, the scrolling message area will show “CHANGE HUMIDIFIER PAD” to indicate maintenance is required.
Thermostat User Menus |
| |
Status |
|
|
Parameter | Indications | Comments |
|
|
|
Configuration | HP - Heat Pump | Indication in center of screen shows the |
| DF - Dual Fuel | configuration of the thermostat based on the |
| GH - Gas Heat | equipment connected. |
| ES - Electric System | The type of system with the number of stages |
| AC - Air Conditioner | will be displayed above the or . Additional |
| FN - Fan | system types and stages can be viewed by |
| EH - Electric Heat | pressing or . |
--- Furnace and Air Conditioner
Setup
Parameter | Options | Comments |
|
|
|
Outdoor | bL, On, OFF | bL – (7 Days Programming only) Factory default is |
Temperature |
| (bLink), alternates time display between time and |
Display |
| outdoor temperature. |
|
| On – (0 Days Programming default) The outdoor |
|
| temperature is displayed continuously on the time |
|
| display. |
|
| OFF – Only Time is displayed. |
|
|
|
Heat Pump | OFF, 5° to 50°F | Available only for air handler with heat pump |
Disable (HP) |
| systems. Disables heat pump and turns on electric |
|
| heat below the selected outdoor temperature. |
|
|
|
Dual Fuel | OFF, 5° to 50°F | Available only for furnace with heat pump systems |
Disable (DF) |
| (dual fuel systems). Switches from heat pump to |
|
| fossil fuel equipment (furnace) below the selected |
|
| temperature. |
|
|
|
Air Handler | OFF, Heat Pump | Available only for air handler with heat pump |
Lockout | Disable setting to | systems. Disables electric heat above the selected |
Temperature | 95°F | outdoor temperature. OFF defaults to 50°F. |
(AH) |
|
|
|
|
|
<equipment>_ | No, Yes | Steps the selected equipment through its |
Test |
| sequential mode of operation. |
|
|
|
Reset System | No, Yes | This will reset ALL of the communicating system |
|
| components to their factory set values. |
|
|
|