Warning Messages
Warning Messages
Warning messages in the form of audible alarms and error codes that appear on the display panel screen to alert you to an impending system change. Warnings do not affect operation.
With the exception of the error codes displayed on the screen, only the audible alarm can be turned ON or OFF. Follow the steps in Chapter 3, “To adjust the alarm setting:” on page
The error codes are listed in Table
Table | Error Codes Displayed on the Display Panel Screen | |||
|
|
|
|
|
Error Code |
| Condition | Mode | Action |
|
|
|
|
|
E01 |
| Low battery voltage | Inverting | • Check battery status and recharge if |
|
| shutdown |
| necessary. |
|
| (< 10.5 Vdc) |
| • Check for proper DC cable sizing. |
|
|
|
| • Check for loose connections and tighten if |
|
|
|
| necessary. |
|
|
|
|
|
E02 |
| High battery voltage | Inverting | • Check for external charging sources, such |
|
| shutdown |
| as an over voltage alternator, and |
|
| (> 15.5 Vdc) |
| disconnect if necessary. |
|
|
|
|
|
E03 |
| AC output overload | Inverting | • Reduce the loads connected to the AC |
|
| shutdown |
| outlet of the unit. |
|
|
|
| • Check appliances that have |
|
|
|
| ratings and disconnect if necessary. |
|
|
|
|
|
E04 |
| Inverting | • Reduce the loads connected to the AC | |
|
| shutdown |
| outlet of the unit. |
|
|
|
| • Check that the ventilation grille is not |
|
|
|
| blocked. |
|
|
|
| • Check for ambient temperature and move |
|
|
|
| the unit to a cooler location whenever |
|
|
|
| possible. |
|
|
|
|
|
E05 |
| Low battery voltage | Inverting | • Check battery status and recharge if |
|
| detected |
| necessary. |
|
| (< 11.0 Vdc) |
| • Check for proper DC cable sizing. |
|
|
|
| • Check for loose connections and tighten if |
|
|
|
| necessary. |
|
|
|
|
|
E06 |
| AC output overload | Inverting | • Reduce the loads connected to the AC |
|
| warning |
| outlet of the unit. |
|
|
|
|
|