Xantrex Technology HF 1800 1 Charging Current Guidelines, AC Input Circuit, Maximum By-pass AC

Models: HF 1800 HF 1000

1 78
Download 78 pages 18.24 Kb
Page 33
Image 33
Table 3-1Charging Current Guidelines

Adjusting Display, Alarm, and Charging Current Settings

Table 3-1Charging Current Guidelines

AC Input Circuit

Charger DC Current Setting

Maximum By-pass AC

Breaker or fuse

(Amps)

 

Current Available (Amps)

size (Amps)

 

 

 

 

Freedom HF 1000

Freedom HF 1800

Freedom HF 1000

Freedom HF 1800

 

 

 

 

 

15

2

2

13.5

13.5

 

5

10

12.5

11.0

 

10

20

11.0

8.5

 

20

40

8.5

3.5

20

2

2

18.5

18.5

 

5

10

17.5

16

 

10

20

16

13.5

 

20

40

13.5

8.5

30

2

2

28.5

28.5

 

5

10

27.5

26

 

10

20

26

23.5

 

20

40

23.5

18.5

 

 

 

 

 

975-0390-01-01

3–5

Page 33
Image 33
Xantrex Technology HF 1800 1 Charging Current Guidelines, AC Input Circuit, Maximum By-pass AC, Breaker or fuse, Amps