Specifications
Inverter specifications (Continued)
Shutdowns and Restarts |
|
|
|
DC low voltage shutdown | 1. Battery voltage drops below |
| 10.6 ± 0.15 Vdc at heavy loads (more than |
| 150 W) or 10.8 Vdc at light loads (less than |
| 150 W) for more than 4 min and 10 sec |
| (± 30 s) |
| 2. Battery voltage is below 10.4 ± 0.2 Vdc for |
| 3 seconds |
|
|
DC low voltage restart | 13.0 ± 0.15 Vdc |
|
|
DC high voltage shutdown | 16.0 ± 0.2 Vdc |
|
|
DC high voltage restart | Less than 16.0 Vdc same as DC high voltage |
| shutdown. There is no hysteresis. |
|
|
Charger Specifications
All charging specifications are at nominal conditions: 77 °F (25 °C), 14.0 Vdc at 50 A charging, 120 Vac, 60 Hz unless otherwise specified.
Charger specifications
Charging method | • |
| compensation. |
| See Figure |
| • Algorithm for generic flooded batteries only |
| • No equalization mode |
|
|
AC input voltage | |
|
|
AC input frequency | |
|
|
Minimum battery voltage | 7 Vdc |
| The charger does not operate below this level |
|
|
Maximum charger input | 13.0 Aac rms |
current |
|
|
|
Maximum charge rate | 50 ± 5 ADC. |
| See Figure |
| temperature derating curve” on page |
|
|
Charger efficiency | Greater than 80% |
|
|