Xantrex Technology IP1012 AL manual Troubleshooting, Common Problems

Models: IP1012 AL

1 52
Download 52 pages 11.23 Kb
Page 34
Image 34
Troubleshooting

Troubleshooting

Troubleshooting

Common Problems

The unit shuts down during operation for four main reasons:

low battery—when the battery reaches approximately 10.6 Vdc for more than four minutes with loads greater than 150 watts , or

10.8 Vdc for loads less than 150 watts. Low battery shutdown also occurs when battery voltage reaches 10.4 Vdc for three seconds.

high battery—when the battery voltage exceeds 16 Vdc

overload—when the AC load connected to the inverter exceeds the rated load

over temperature—when the internal temperature thresholds are reached

Table 4-1 lists problems you may encounter and offers suggestions to fix them.

Table 4-1Troubleshooting reference

Symptom

Possible Problem

Remedy

 

 

 

Loads will not start when there

Inverter is not turned on.

Turn the inverter on.

is no shorepower.

Batteries are at low voltage.

Recharge the batteries by running

 

 

 

the engine or connecting to

 

Inverter is too hot

shorepower.

 

Wait until the inverter has cooled

 

 

 

 

down.

 

 

 

Loads stop running almost as

Load is too heavy.

Reduce the load.

soon as they start.

Batteries are at low voltage

Recharge the batteries by running

 

 

level.

the engine or connecting to

 

Bad battery cable or corroded

shorepower.

 

Check the cable and connectors.

 

battery terminals.

 

Batteries are in poor condition.

Test and replace, if necessary

 

 

 

4–2

975-0337-01-01

Page 34
Image 34