Advanced Functions

F03 DISPLAYORSETBATTERYTEMPERATURE

If there is no external temp sensor and F16 is OFF (factory default), this function sets ambient battery temperature used to caluculate rate corrected battery capacity which drives the LED bar graph and the Time remaining display. Feature not available on units with serial numbers prior to 05000.

DEFAULT: 20 °C

RANGE: 0–40 °C

STEP: 1 °C

If F16 is ON and an optional external temperature sensor is connected between Pin 6 and Pin 8 (ground), F03 will display temperature (0–99 °C). Temperature will continue to be displayed until one of the two front panel buttons is pressed. Active Temperature display is annunciated by the absence of front panel status indicators. If 0 is displayed at normal (~ 20 °C) temperatures, an open temperature probe should be assumed. If >99 is displayed at normal temperatures, a shorted probe should be suspected.

F04 TURN ON KWHRS DISPLAY

Kilowatt hours are displayed in the Ah mode. (Note: The kWh display does not take into account Charging Efficiency. As a condition for a recalculation of the CEF and an automatic reset of amp hours to zero, 100% of the energy removed from the battery must be returned. The number in the kWh display must be zero or positive to allow a recalculation of the CEF and an automatic reset to zero. You may use this function to verify that this condition has been met.)

DEFAULT: OFF RANGE: OFF or ON

F05 USEALTERNATIVEENERGY(AE)DEFAULTS

Changes time to meet Charged Parameters to one minute from the normal five minutes. (Also consider changing Charged Current to 4%.) DEFAULT: OFF RANGE: OFF or ON

31