Advanced Functions
F06 MANUALLY SET CEF (Not Recommended)
Allows manual setup of CEF. Displayed as two digits. Default display A90 indicates automatic CEF recalculation feature active. Returning to A90 from a user CEF turns the automatic CEF feature back on. A
DEFAULT:A90 RANGE:
F07 SETTEMPERATURECOEFFICIENT
Compensates for capacity change with temp. ~ 0.5% Cap/°C. This coefficient must be supplied by the battery manufacturer. The default value is typical for lead acid liquid or gelled batteries.
DEFAULT: 0.5 RANGE:
F08 SETPEUKERTEXPONENT
Sets exponent for Peukert’s equation. A setting of 1.0 defeats Peukert's calculation. See pages
F09 SETDISCHARGEFLOOR
Sets the discharge floor used to calculate bar graph status and time of operation remaining functions. The factory default is to calculate time remaining, and bar graph based on a
To ensure a margin of safety you may wish to set a different discharge floor. You may wish to set 80% or some other discharge floor for your bar graph.