Alarm Functions

Refer to F14 in the Owner's Manual

Functions F10, F11, and F12 define operation of the Visual Low Battery Alarm as follows:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F11

 

 

 

 

 

 

TURNS ON Low Battery

 

 

 

 

 

 

 

Alarm at a set % of rate-

 

 

 

 

 

 

 

compensated amp hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

discharged

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10% Discharged

 

 

 

Amp-Hour

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALARM ON

 

 

 

Capacity of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Settable Range

 

 

 

E.G. 100 Ah

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80% Discharged

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F10

TURNS OFF Low

Battery Alarm when

amp hours are restored

0% Discharged

ALARM OFF

Settable Range

70% Discharged

F10 LOWBATTERYALARM OFF (RECHARGE)SETPOINT Once the Low Battery Alarm is activated, recharging the battery to this point turns the alarm OFF. This recharged point must always be at least 10% higher than Low Battery Line closure point.

DEFAULT: 70% RANGE: 0%–70% STEP: 5%

F11 LOW BATTERY ALARM ON SET POINT

Sets when the Low Battery Alarm goes ON point based on percent of amp hours discharged. F11 is displayed as a percentage: i.e. 10 is 10% discharged. F11 may set anywhere in its range but at least 10% below the F10 Low Battery Alarm OFF Set Point set point.

DEFAULT: 80% RANGE: 10%–80%

STEP: 5%