Operation
28975-0125-02-01
You can also enter or exit Power Save mode on the System Settings menu by
selecting Desired Mode and scrolling to PowerSave as shown in Figure 2-4.
Returning to
Operate mode If an inverter/charger supplies power to the network, applying AC input with
utility power or generator power automatically returns the system to Operate
mode.
Safe Mode
Characteristics Selecting Safe mode stops the generator (if it is running) and puts the System
Control Panel (and all Xanbus-enabled devices) into Safe mode. While in Safe
mode, the System Control Panel remains powered, listening to and reporting its
status to the network. However, the oupt ut power of all Xanbus- ena bled devic es is
disabled and all inverting, charging, and generator starting activity stops. In Safe
mode, the MS2000 will not pass AC.
In Safe mode, the MS2000 continues to communicate, but the inverting and
charging functions are disabled.
When to use Use Safe mode when you are adding or removing devices from the network.
Authorized service personnel must also put the System Control Panel in Safe
mode before performing software upgrades and diagnostics with the Xantrex
Diagnostic Tool.
If the System Control Panel is powered off while in Safe mode, it will be in Safe
mode when it is powered up again.
To return to Operate mode:
On the System Settings menu, under Desired Mode, select Operate.
Figure 2-4
Power Sa ve Mod e
CAUTION: Unexpected behavior
Before installing or removing a device on the ne twork, put the network into Safe
mode. This prevents unexpected behaviour.