OPERATION

AC CURRENT LEVEL

The maximum current draw into the AC HOT IN 1 terminal can be adjusted by the SET GRID (AC1) AMPS AC menu item. The maximum current draw into the AC HOT IN 2 terminal can be adjusted by the SET GEN (AC2) AMPS AC menu item. These adjustments are used to “back off” the battery charger’s AC current draw while other AC loads are being powered through the inverter. This prevents the overloading of the AC source and prevents nuisance tripping of the AC source circuit breakers.

FREQUENCY

AC HOT IN 1 is the Utility Power connection point. The frequency tolerance is 53 to 67 Hz for 60 Hz models (44 to 56 for 50 Hz models). The typical transfer delay is approximately 30 seconds once the AC HOT IN 1 terminals are energized. When the SELL mode is enabled from the SET GRID USAGE menu item, the transfer delay period is typically 90 seconds and the frequency tolerance is restricted to 58 to 62 Hz for 60 Hz models (48 to 52 Hz for 50 Hz models).

AC HOT IN 2 is used as a fuel-powered generator connection point. There is a default 60-second delay before transfer occurs. This gives the generator time to stabilize before being loaded. Frequency tolerance is 53 to 67 Hz for 60 Hz models (44 to 56 for 50 Hz models). The fuel-powered generator must be stable for the inverter to synchronize and connect.

DELAY PERIOD

The delay period, approximately 30 seconds, occurs after the AC source has been applied to the AC HOT IN 1 terminal. If SELL mode is enabled (from the SET GRID USAGE menu item under the INVERTER SETUP (9) menu heading) and a power outage occurs, reconnection back to the utility power will be delayed for a period of at least 90 seconds. This delay allows the utility distribution system to stabilize before the inverter resumes selling power back to the utility. It is not adjustable.

The delay period for the AC HOT IN 2 terminal is adjustable through the SET GEN WARMUP SECONDS menu item under the GEN STARTING DETAILS (13) menu heading. This allows the generator to reach a stable operating condition before being loaded. The default generator warm-up period is 60 seconds. Once warmed up, the inverter synchronizes to the generator. If the AC source is not stable, the inverter may not be able to synchronize and will not connect. If the generator runs for 5 minutes without the inverter being able to connect, then the generator will be shut off and the ERROR LED indicator will be illuminated. A GENERATOR SYNC, YES error condition will be displayed in the ERROR CAUSES (5) menu heading on the Control Panel.

RECOMMENDED BATTERY CHARGER SETTINGS

The settings for the battery charger primarily depend upon the battery chemistry and construction. Other factors such as usage, age and battery bank size need to be considered as well. The battery charger settings will automatically adjust if the temperature compensation sensor is installed. If it is not installed, the settings should be adjusted manually to allow for the typical battery temperature. This may require seasonal readjustment for optimum performance.

The default settings are typical values for liquid, lead acid battery applications. They will work satisfactorily for many systems.

CAUTION: To prevent battery damage and achieve maximum performance, adjust the battery charger settings to the manufacturer’s recommendations. NiCad (or alkaline) battery users must also adjust the SET TEMP COMP menu item setting. The battery charger settings are located under the BATTERY CHARGER (10) menu heading in the SETUP MENU.

The SET MAX CHARGE AMPS AC menu item will need to be reduced if you are using a small battery bank. High charge rates can cause a small battery to overheat. This may cause damage and is not an efficient way to recharge the battery. With the Control Panel, adjust the charger for a maximum rate that is less than 1/5 of the battery capacity for efficient recharging. For example, if the battery is rated at 500 amp-hours, set the maximum charge rate for 100 amps DC. Since the setting is adjusted in amps AC drawn by the battery charger, divide the DC charge rate by 8 for 12 volt systems, 4 for 24 volt systems and 2 for 48 volt systems (these factors are for 120 VAC systems and include the power lost in the battery charger). If the example battery bank of 500 amp hours was a 24 volt system, the maximum AC amps setting should be around 25 amps AC (500 x 1/5 = 100 amps DC, 100 / 4 = 25 amps AC.)

Page

66

2001 Xantrex Technology, Inc.

Telephone: 360/435-8826

SW Series Inverter/Charger

5916 - 195th Street N. E.

Fax: 360/435-2229

Part No. 2031-5

Arlington, WA 98223

www.traceengineering.com

Rev. C: February 2001

Page 74
Image 74
Xantrex Technology SW Series owner manual Recommended Battery Charger Settings, AC Current Level, Frequency, Delay Period

SW Series specifications

Xantrex Technology has established itself as a leader in innovative power solutions, and its SW Series inverters epitomizes this commitment to quality and efficiency. Designed for both standalone and grid-tied applications, the SW Series offers versatile power management for a range of residential and commercial needs.

At the heart of the SW Series is its advanced pure sine wave output, ensuring clean and reliable electricity suitable for sensitive electronics. This feature makes it an excellent choice for applications such as solar energy systems, where it provides high-quality power for a variety of devices, from household appliances to complex machinery.

One of the key characteristics of the SW Series is its modular design, which allows for easy installation and scalability. This modularity enables users to expand their power system as their energy needs grow, making it an ideal choice for both small and large installations. The inverters come equipped with a user-friendly interface, providing clear information on system performance, battery status, and more, ensuring that users can effectively monitor and manage their energy consumption.

The SW Series inverters also incorporate cutting-edge technology, such as the patented Power Factor Correction (PFC) feature, which optimizes energy efficiency by reducing harmonic distortion. This translates into less wasted electricity and lower energy costs, making it an environmentally friendly option for users looking to reduce their carbon footprint.

Another notable feature of the SW Series is its ability to operate in extreme conditions. Built with robust components and advanced thermal management systems, these inverters can withstand a wide range of temperatures and environmental challenges, ensuring reliable performance in various settings. This durability makes them suitable for off-grid applications, including remote cabins, RVs, and boats.

Furthermore, the SW Series supports a variety of battery types, including lithium-ion, AGM, and gel batteries, offering flexibility for users to choose the best energy storage solution for their needs. The sophisticated battery management system ensures optimal charging and discharging, prolonging the lifespan of the batteries and enhancing the overall efficiency of the power system.

In summary, Xantrex Technology's SW Series inverters stand out for their pure sine wave output, modular design, energy efficiency features, and robust performance in challenging conditions. With their versatility and advanced technology, they cater to the evolving needs of today’s power consumers, making them a compelling choice in the modern energy landscape.