Xantrex Technology SW Series Setup Menu Map, Page 35, Menu System, Menu Headings, Menu Items

Models: SW Series

1 152
Download 152 pages 56.77 Kb
Page 43
Image 43
SETUP MENU MAP

MENU SYSTEM

SETUP MENU MAP

The SETUP MENU provides all the controls and settings needed when installing or adjusting the system. To access the SETUP MENU, press both the red ON/OFF MENU and green GEN MENU buttons on the Control Panel at the same time. To exit the SETUP MENU, press the red ON/OFF MENU button or press the down MENU HEADING button until you reach the USER MENU (menu headings 1-8).

MENU HEADINGS

Inverter Setup

 

Battery Charging

 

AC Inputs

 

 

Gen Auto Start

 

 

Gen starting

 

 

Auxiliary Relays

9

 

10

 

 

11

 

setup

12

 

details

13

 

R9 R10 R11

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MENU ITEMS

Set Grid Usage

FLT SELL SLT LBX

Set Low battery cut out VDC 11.0

Set LBCO delay

minutes

10

 

Set Low battery

cut in VDC

13.0

 

Set High battery

cut out VDC

16.0

 

 

Set search

 

watts

48

 

 

Set search

 

spacing

59

Set Bulk

 

volts DC

14.4

 

Set Absorption

time h:m

02:00

 

 

Set Float

 

volts DC

13.4

 

Set Equalize

volts DC

14.4

 

Set Equalize

time h:m

02:00

 

Set Max Charge

amps AC

20

 

 

Set Temp Comp

LeadAcid NiCad

Set Grid (AC1)

amps AC

60

 

 

Set Gen (AC2)

 

amps AC

30

 

Set Input lower

limit VAC

108

 

Set Input upper

limit VAC

132

Set Load Start

amp AC

20

 

Set Load Start

delay min

5.0

 

Set Load Stop

delay min

5.0

 

Set 24 hr start

volts DC

12.3

 

Set 2 hr start

volts DC

11.8

 

Set 15 min start

volts DC

11.3

 

Read LBCO 30 sec

start VDC

11.0

 

Set Exercise

period days

30

 

Set Maximum run

time h:m

08:00

Page Set Max Run time Manual background to 0 to defeat.

Manual background Set Exercise to 0 Manual background to defeat.

Manual background See menu 9 to Manual background to set LBCO.

Set RY7 Function GlowStop Run

Set Gen warmup

seconds 60

Set Pre Crank

seconds 10

Set Max Cranking

seconds 10

Set Post Crank

seconds 30

Set Relay 9

volts DC

14.5

 

R9 Hysteresis

volts DC

01.0

 

Set Relay 10

volts DC

14.8

 

R10 Hysteresis

volts DC

01.0

 

Set Relay 11

volts DC

15.0

 

R11 Hysteresis

volts DC

01.0

Close on batt >

setpoint.

 

Open on

batt <

Manual background setpoint - Hys

Manual background Relays have 2 Manual background second delay on

Manual background Close, 0.1 sec Manual background delay on open

 

 

Bulk Charge

 

 

Low Battery

 

 

Battery Selling

 

Grid Usage Timer

 

Information file

 

End Setup Menu

 

 

Trigger Timer 15

 

Transfer (LBX) 16

 

 

17

 

 

18

 

battery

19

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set Start Bulk

 

Set Low Battery

 

Set Battery Sell

 

Start Charge

 

Batt temp comp

 

 

 

 

 

time

00:00

 

TransferVDC

11.3

 

volts DC

13.4

 

time

21:00

 

changes battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To disable timer

 

Set Low battery

 

Set Max Sell

 

 

End Charge

 

 

voltage reading

 

 

 

 

 

set to 00:00

 

 

cut in VDC

13.0

 

amps AC

30

 

time

21:00

 

away from actual

 

 

 

 

 

If grid timer

 

 

See menu 9 to

 

 

See menu 9 to

 

 

After Start

 

 

HBCO resets at:

 

 

 

 

 

active set bulk

 

enable LBX mode.

 

enable SELL mode.

 

Charge time:

 

 

6v/48, 3v/24 and

 

 

 

 

 

time after start

 

Make sure LBX is

 

Make sure LBX is

 

SELL mode

 

 

1.5v/12v under

 

 

 

 

 

charge time.

 

 

above LBCO volts.

 

above LBCO volts.

 

charges battery.

 

HBCO.

 

 

 

 

 

In SLT mode don’t

 

 

 

 

 

 

 

FLT mode

 

 

LowBattTransfer

 

 

 

 

 

disable this

 

 

 

 

 

 

 

 

charges battery

 

used in LBX, FLT

 

 

 

 

 

timer. It is the

 

 

 

 

 

 

 

After End Charge

 

Modes only. Goes

 

 

 

 

 

daily chg time.

 

 

 

 

 

 

 

time:

 

 

back to battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SELL mode sells

 

at LowBattCutIn

 

 

 

 

 

 

 

 

 

 

 

 

 

 

battery to AC1.

 

(aka LBCI).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLT mode drops

 

For LBX mode set

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC1 and inverts

 

below LBCI so

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Timer on when

 

 

charger won’t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

start < > end;

 

cycle batteries

 

 

 

 

 

 

 

 

 

 

 

 

 

 

timer off when

 

up and down and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

start = end

 

 

set LBCO below.

 

 

 

Manual background Sell and float Manual background modes use timer

Manual background SLT and LBX mode ignore timer

2001 Xantrex Technology, Inc.

Telephone: 360/435-8826

SW Series Inverter/Charger

5916 - 195th Street N. E.

Fax: 360/435-2229

Part No. 2031-5

Arlington, WA 98223

www.traceengineering.com

Rev. C: February 2001

Page

35

Page 43
Image 43
Xantrex Technology SW Series Setup Menu Map, Page 35, Menu System, Menu Headings, Menu Items, Telephone 360/435-8826