Xantrex Technology SW Series Contrast Control, Reset To Factory Defaults Button, Menu Buttons

Models: SW Series

1 152
Download 152 pages 56.77 Kb
Page 18
Image 18
CONTRAST CONTROL

CONTROLS, INDICATORS AND COMPONENTS

CONTRAST CONTROL

The CONTRAST adjustment enables you to adjust the contrast of the LCD display screen to accommodate changing lighting conditions. Less contrast is usually preferable in brighter lighting conditions.

RESET TO FACTORY DEFAULTS BUTTON

The RESET TO FACTORY DEFAULTS button returns all of the inverter settings (except for the TIME OF DAY settings) to the factory default values. The default values will be re-entered only when this button is pushed from a specific menu item in the USER MENU. You must first select the TRACE ENGINEERING

(3)menu heading and then go to the first menu item, which will display “PRESS RESET NOW FOR DEFAULTS”. Once this reset button is pressed from this menu item, you must reprogram all settings required by your installation into the inverter.

Removing DC power from the inverter will also return the inverter to the factory default values (including the TIME OF DAY settings). You must then reprogram the inverter with the required settings for proper operation of your system. Recording your settings on the USER SETTINGS WORKSHEET, in the TECHNICAL INFORMATION section of this manual, will make the reprogramming of the inverter much easier.

The reset button is also used to re-synchronize the remote control (SWRC) display if the characters become jumbled. Pressing the reset button anywhere in the menu system (except the PRESS RESET NOW FOR DEFAULTS menu item) will re-synchronize the display, but the default values will not be reset.

MENU BUTTONS

ON/OFF MENU BUTTON (Red)

Pressing the red ON/OFF MENU button at any time will take you directly to the SET INVERTER menu item of the INVERTER MODE (1) menu heading. There are four options available from this menu item. The first letter of the selected item will be underlined. Pressing the red ON/OFF MENU button will move the cursor one position to the right, selecting the next item. You can also use the SET POINTS buttons to move either right or left.

GEN MENU BUTTON (Green)

Pressing the green GEN MENU button at any time will display the SET GENERATOR menu item of the GENERATOR MODE (2) menu heading. There are four options available from this menu. The first letter of the selected item will be underlined. Pressing the green GEN MENU button will move the cursor one position to the right, selecting the next item. You can also use the SET POINTS buttons to move either right or left.

MENU ACCESS/ADJUSTMENT BUTTONS (Black)

The MENU HEADING buttons are used to move either up or down through the selection of menu headings. Once a menu heading is selected, the MENU ITEM buttons are used to move up or down through the list of related menu items. The SET POINTS buttons change the value of a parameter or select a mode, for the selected menu item.

LED STATUS INDICATORS

The Control Panel features eight colored LED indicators that identify the various operating conditions of the inverter. Unless otherwise indicated, the LED’s will be "solid" in appearance, when illuminated.

LINE TIE (Yellow)

Selecting SELL from the GRID USAGE menu item under the INVERTER SETUP (9) menu heading will enable sell mode. This should only be done with utility connected systems and after you have received the approval of the local utility. This mode allows excess power to be sent into the utility grid.

INVERTING (Yellow)

The inverter is operational and AC output is available. If this LED is blinking, the inverter is in the search mode and is looking for an AC load greater than the SET SEARCH WATTS setting.

Page

10

2001 Xantrex Technology, Inc.

Telephone: 360/435-8826

SW Series Inverter/Charger

5916 - 195th Street N. E.

Fax: 360/435-2229

Part No. 2031-5

Arlington, WA 98223

www.traceengineering.com

Rev. C: February 2001

Page 18
Image 18
Xantrex Technology SW Series Contrast Control, Reset To Factory Defaults Button, Menu Buttons, Led Status Indicators