OPERATION

GENERATOR SUPPORT/OVERLOAD PROTECTION

This battery charger is quite powerful and, without limits, could overload a generator. When the generator is running, it has to power both the battery charger and any connected AC loads. If the AC load current, combined with the charge current, exceeds the SET GEN (AC2) AMPS AC setting, the charge rate will automatically be reduced to avoid overloading the generator or tripping its circuit breaker.

If the amount of current demanded by the AC load is greater than the GEN (AC2) AMPS AC setting, the inverter is capable of supplementing the generator’s power. The inverter attempts to hold the current drawn from the generator at the setting of the GEN (AC2) AMPS AC. This allows the generator to start larger loads than it could normally and reduces the load on the generator during motor start-ups.

Generator support is also available if AC voltage falls to the SET INPUT LOWER LIMIT VAC. In this case, the inverter will assist the generator as long as there is power flowing from the generator to the load. This is typically used when a large AC load is being operated and the generator’s AC output voltage drops.

For example, if you have a 20 amp generator and the GEN SIZE AMPS AC setting is at 15 amps, the inverter will start providing additional power from the batteries whenever the load reaches 15 amps or higher (even though it may not be required). When setting the GEN SIZE AMPS AC value, allow for headroom but do not set the value too low.

While the inverter is supporting the generator, the BULK or FLOAT LED Indicator will remain on even though the inverter may not be battery charging. The INVERTER/CHARGER AMPS AC meter will indicate the support process by displaying “negative” current flowing from the inverter to the loads. The INPUT AMPS AC will also drop during this process while the LOAD AMPS AC remains the same.

120 VAC VS. 120/240 VAC GENERATORS

In the US, generators are available with either 120/240 VAC “split phase” or 120 VAC only output. Some generators can be rewired in the field, or have a switch, for changing from one output to the other. If a system uses only one inverter, having the generator put out all of its power at 120 VAC is advantageous. If two inverters are used, having the generator wired for 120/240 VAC output is better.

If you are using one inverter and can not rewire your generator for 120 VAC, or have a combination of 120 and 240 VAC loads which need to be operated, you may need to include a balancing transformer to allow full use of the generator output at 120 VAC. This allows the battery charger to use power from both “halves” of the generator, instead of only half of it. Xantrex offers a balancing transformer (Part Number T-

240)for this purpose. See OTHER PRODUCTS section on page 129 or contact your inverter supplier for more information.

If your generator can be wired for 120 VAC output and you are using only one inverter, 240 VAC loads can be operated from the system by using a transformer in a step-up configuration. This is common for deep well submersible well pumps. If the step-up is done on the pump side of the pressure switch or manual switch for the pump (run 120 VAC through the switch then step it up to 240 VAC), the transformer will not interfere with using the search mode or increase idle current draw by the inverter when the pump is off.

When two inverters are operating in a “series stacked” configuration (120/240 VAC); each inverter operates as a separate inverter. One inverter can be battery charging with the excess power from one half of the generator, while the other inverter is supporting the generator by operating in parallel to support a heavy 120 VAC load on that half of the system. This allows greater utilization of limited system capacity and is very useful when starting large 120 VAC loads such as water pumps or compressors.

Two 120 VAC/60 HZ inverters can be used to provide 240 VAC. This provides both 120 and 240 VAC since a center “neutral” is provided between the two inverters. If a 240 VAC only AC source is connected to the AC input terminals of the inverter without this center neutral, unacceptable operation will result. To allow connection of a 240 VAC only source, a small (500 VA) autotransformer must be connected across the 240 VAC input and to the AC neutral terminals of the inverters. This will allow the inverter to operate properly. No transformer is required on the AC output side - the 240 VAC can be taken directly from the two AC hot output terminals (one from each inverter).

Page

72

2001 Xantrex Technology, Inc.

Telephone: 360/435-8826

SW Series Inverter/Charger

5916 - 195th Street N. E.

Fax: 360/435-2229

Part No. 2031-5

Arlington, WA 98223

www.traceengineering.com

Rev. C: February 2001

Page 80
Image 80
Xantrex Technology SW Series owner manual Generator SUPPORT/OVERLOAD Protection, VAC VS /240 VAC Generators

SW Series specifications

Xantrex Technology has established itself as a leader in innovative power solutions, and its SW Series inverters epitomizes this commitment to quality and efficiency. Designed for both standalone and grid-tied applications, the SW Series offers versatile power management for a range of residential and commercial needs.

At the heart of the SW Series is its advanced pure sine wave output, ensuring clean and reliable electricity suitable for sensitive electronics. This feature makes it an excellent choice for applications such as solar energy systems, where it provides high-quality power for a variety of devices, from household appliances to complex machinery.

One of the key characteristics of the SW Series is its modular design, which allows for easy installation and scalability. This modularity enables users to expand their power system as their energy needs grow, making it an ideal choice for both small and large installations. The inverters come equipped with a user-friendly interface, providing clear information on system performance, battery status, and more, ensuring that users can effectively monitor and manage their energy consumption.

The SW Series inverters also incorporate cutting-edge technology, such as the patented Power Factor Correction (PFC) feature, which optimizes energy efficiency by reducing harmonic distortion. This translates into less wasted electricity and lower energy costs, making it an environmentally friendly option for users looking to reduce their carbon footprint.

Another notable feature of the SW Series is its ability to operate in extreme conditions. Built with robust components and advanced thermal management systems, these inverters can withstand a wide range of temperatures and environmental challenges, ensuring reliable performance in various settings. This durability makes them suitable for off-grid applications, including remote cabins, RVs, and boats.

Furthermore, the SW Series supports a variety of battery types, including lithium-ion, AGM, and gel batteries, offering flexibility for users to choose the best energy storage solution for their needs. The sophisticated battery management system ensures optimal charging and discharging, prolonging the lifespan of the batteries and enhancing the overall efficiency of the power system.

In summary, Xantrex Technology's SW Series inverters stand out for their pure sine wave output, modular design, energy efficiency features, and robust performance in challenging conditions. With their versatility and advanced technology, they cater to the evolving needs of today’s power consumers, making them a compelling choice in the modern energy landscape.