Preparing the Mounting Location for the XADC and Panel
To prepare the XADC and panel mounting location:
1. Cut a mounting hole (12in. × 12 1/8 in. – 305 mm × 307 mm) for the
connected XADC and panel, or
follow the instructions in “Preparing the Mounting Location for the XADC”
on page 13 for the XADC and cut a mounting hole (12 in. × 8in. – 305 mm ×
203 mm) for the panel, or
use an existing hole from a previous converter installation.
2. Place the XADC and panel into the mounting hole and hold them against the
mounting surface.
3. Mark the positions of the mounting screws, and then remove the XADC and
panel from the mounting hole.
Connection Types for AC and DC
Both the AC and DC busses use a screw-in lug type of connection.
To perform connections with the screw-in type lug:
1. Ensure the screw is loosened.
2. Slide the cable into the hole behind the screw.
3. Tighten the screw (see Table1 on page 24 for torque values).
Connecting the DC to the Panel
See “Connection Types for AC and DC” on page 18 for information on the
connections used on the busses.
When following the procedure, see Table2 on page 24 for wire lengths and
battery DC fuse ratings and Table1 on page 24 for torque values.
To connect the DC loads:
See Figure 14 for additional information.
1. Install a UL/CSA approved strain relief on the incoming negative (-) black
cables and incoming positive (+) red cables. Tighten the clamping ring (but
not the clamp screws) on the strain relief.
2. Route the incoming negative (-) black cables and incoming positive (+) red
cables through the knockouts in the back of the panel.
WARNING: Shock hazard
Ensure that the DC battery is physically disconnected, or that the DC disconnect or
breaker is open before attempting any installation.
Important:
Multiple cables can be placed into a strain relief. Check the strain relief
manufacturer’s datasheet for maximum number of cables allowed.